Plan Review Notes
Plan Review Notes For Permit 21031236
Permit Number 21031236
Review Stop E
Sequence Number 1
Notes
Date Text
2021-08-18 08:59:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ELECTRICAL PLAN LAYOUT AND PLUMBING LAYOUT DON'T MATCH,
 FRONT COUNTER?
  
 PLEASE INDICATE GFCI PROTECTION PER 210.8(B) NOT ABLE
 TO DISTINGUISH BETWEEN REGULAR AND GFI OUTLETS PER
 PLAN.
  
 PLEASE SUBMIT RISER DIAGRAM FOR SERVICE AND IT'S
 LOCATION 215.5
  
 NO EXIT OR EMERGENCY LIGHTS SHOWN NFPA 101