| Plan Review Notes For Permit 21031236 |
| Permit Number |
21031236 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-18 10:27:20 | BUILDOUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) UNABLE TO DETERMINE NEW FROM EXISTING - PLEASE | | | PROVIDE AN EXISTING PREVIOUSLY PERMITTED FLOOR PLAN | | | (EXISTING VS PROPOSED). | | | 2) PROVIDE ALL DETAILS FOR ITEMS NOT PREVIOUSLY | | | PERMITTED - MEZZANINE OR 2ND FLOOR, STAIRS, STAIR | | | ENCLOSURE, ACCESSIBLE RESTROOM ETC. | | | 3) SHOW CUSTOMER COUNTER SIZE, HEIGHT AND CLEAR FLOOR | | | SPACE PER FBC ACCESSIBILITY 904 | | | 4) PLEASE SHOW BUILDING CONSTRUCTION TYPE PER FBC | | | CHAPTER 6 | | | 5) PLEASE SHOW THE ADJACENT TENANT USE AND TENANT | | | SEPARATION WALL HOURLY FIRE RATING TO COMPLY WITH FBC | | | 508 | | | 6) FLOOR PLAN SHOWS THE USE OF ASCE 7-10 - SHOULD BE | | | ASCE 7-16 PER FBC CHAPTER 35 | | | 7) PLEASE SHOW THE USE (OCCUPANCY CLASSIFICATION) FOR | | | THE SPACE PER FBC CHAPTER 3 |
|