Plan Review Notes
Plan Review Notes For Permit 21031236
Permit Number 21031236
Review Stop B
Sequence Number 1
Notes
Date Text
2021-08-18 10:27:20BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) UNABLE TO DETERMINE NEW FROM EXISTING - PLEASE
 PROVIDE AN EXISTING PREVIOUSLY PERMITTED FLOOR PLAN
 (EXISTING VS PROPOSED).
 2) PROVIDE ALL DETAILS FOR ITEMS NOT PREVIOUSLY
 PERMITTED - MEZZANINE OR 2ND FLOOR, STAIRS, STAIR
 ENCLOSURE, ACCESSIBLE RESTROOM ETC.
 3) SHOW CUSTOMER COUNTER SIZE, HEIGHT AND CLEAR FLOOR
 SPACE PER FBC ACCESSIBILITY 904
 4) PLEASE SHOW BUILDING CONSTRUCTION TYPE PER FBC
 CHAPTER 6
 5) PLEASE SHOW THE ADJACENT TENANT USE AND TENANT
 SEPARATION WALL HOURLY FIRE RATING TO COMPLY WITH FBC
 508
 6) FLOOR PLAN SHOWS THE USE OF ASCE 7-10 - SHOULD BE
 ASCE 7-16 PER FBC CHAPTER 35
 7) PLEASE SHOW THE USE (OCCUPANCY CLASSIFICATION) FOR
 THE SPACE PER FBC CHAPTER 3