| 2021-04-14 12:46:00 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21031226 |
| | 4/14/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-1: THE PLAN SHEET DOES NOT BEAR THE NAME, |
| | TITLE BLOCK, SIGNATURE OR SEAL OF THE PERSON WHO |
| | PREPARED THE DESIGN- SECTION 107.2.1 WPB. PLEASE NOTE |
| | THE FOLLOWING: |
| | ALL PLANS AND DOCUMENTS PREPARED BY A FL. LICENSED |
| | ENGINEER OR ARCHITECT ARE TO SIGNED, SEALED AND DATE |
| | ORIGINALS. PLANS TRANSMITTED ELECTRONICALLY SHALL BEAR |
| | THE DIGITAL SIGNATURES AND SEALS OF EITHER THE ENGINEER |
| | OR ARCHITECT- FL. STATUTES 471.025 & 481.221, AND FAC |
| | 61G15-23.005 & 61G1-16.005. |
| | FL. LICENSED CONTRACTORS OR QUALIFIERS WHO PREPARE |
| | DRAWINGS SHALL PROVIDE HIS/HER SIGNATURE ON THEM- |
| | SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) |
| | & 471.025. A TITLE BLOCK ON THE DRAWING THAT INCLUDES |
| | CONTRACTOR OR COMPANY NAME AND LICENSE NUMBER IS ALSO |
| | REQUIRED. |
| | |
| | 2) P-1: PLEASE PROVIDE A SHOWER PAN DETAIL- SECTIONS |
| | P2709.1 & P2709.2 FBC RES. |
| | |
| | 3) P-1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE |
| | LISTING MAKE AND MODEL, GALLON SIZE AND EFFICIENCY |
| | RATING. THE DATA IN THE SCHEDULE SHALL MATCH THE DATA |
| | SHOWN ON THE ENERGY COMPLIANCE FORM R405-2020- |
| | 50-GALLON & EFF 0.96- TABLE C404.2 FBC EC. |
| | |
| | 4) P-1: THE RELIEF VALVE DISCHARGE PIPE SHALL TERMINATE |
| | NOT MORE THAN 6 INCHES AND NOT LESS THAN TWO TIMES THE |
| | DISCHARGE PIPE DIAMETER ABOVE THE FLOOR OR WASTE |
| | RECEPTOR FLOOD LEVEL RIM. THE DETAIL INCORRECTLY SHOWS |
| | THE DISCHARGE 4 INCHES FROM THE BOTTOM OF THE PAN NOT |
| | THE FLOOD LEVEL RIM. |
| | |
| | 5) P-1: PROVIDE A THERMAL EXPANSION TANK AND SHOW THE |
| | LOCATION IN THE WATER HEATER DETAIL- SECTION P2903.4 |
| | FBC RES. |
| | |
| | 6) P-1: PROVIDE HEAT TRAPS FOR THE VERTICAL INLET AND |
| | OUTLET PIPE RISERS AT THE WATER HEATER- SECTION |
| | R403.5.5 FBC EC. PLEASE NOTE THE TRAPS ARE NOT REQUIRED |
| | IF THE WATER HEATER IS EQUIPPED WITH INTEGRAL HEAT |
| | TRAPS. |
| | |
| | 7) PLEASE NOTE THAT WHERE A NEW POTABLE WATER SERVICE |
| | BACKFLOW PREVENTER IS REQUIRED: A FL. LICENSED PLUMBING |
| | CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| | INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| | WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF |
| | ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| | THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| | BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| | UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| | FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |