| 2021-09-13 11:55:50 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21031225 |
| | 9/13/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS FOR FURTHER CLARIFICATION. |
| | |
| | 1) FAILED A, B, & C. NO PLUMBING DRAWINGS PROVIDED. |
| | SHEET A-1: PROVIDE PLUMBING PLANS FOR THE ALTERED |
| | TOILET ROOM IN COMPLIANCE WITH SECTIONS 107.2.1 AND |
| | 107.3.5.3.1 WPB, AND FBC- 2020 PLUMBING. PROVIDE THE |
| | FOLLOWING LIST OF ITEMS: |
| | |
| | A) SANITARY DRAINAGE AND WATER RISER DRAWINGS. |
| | |
| | B) PLUMBING FLOOR PLAN LAYOUT DRAWING. |
| | |
| | C) PLUMBING FIXTURE SCHEDULE. |
| | |
| | 3) FAILED ALL ITEMS BELOW EXCEPT C WHICH WAS REMOVED |
| | FROM THE COMMENT LIST. A-1: THE CURRENT TOILET ROOM |
| | DESIGN IS INCOMPLETE AND NOT IN COMPLIANCE WITH THE |
| | FBC- 2020 ACCESSIBILITY CODE. REFER TO SECTIONS 202.3, |
| | 213.1, AND 213.3.1 FBC ACC AND PROVIDE ENLARGED TOILET |
| | ROOM DRAWINGS SHOWING COMPLIANCE WITH THE FOLLOWING |
| | ITEMS- FBC ACC: |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSET- SECTION 604.3. |
| | |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORY- SECTION 606.2. |
| | |
| | D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| | SECTION 604.2. |
| | |
| | E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOOR- SECTION 604.4. |
| | |
| | F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | REFLECTIVE SURFACE- SECTION 603.3. |
| | |
| | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604. |
| | |
| | H) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION |
| | 604.6. |
| | |
| | I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| | 606.2. |
| | |
| | IT APPEARS THAT THE EXISTING WINDOWS BY THE RESTROOM |
| | WOULD HAVE TO BE REMOVED IN ORDER TO MEET COMPLIANCE |
| | WITH THE FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |