| 2021-04-08 12:52:11 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21031225 |
| | 4/8/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-1: PROVIDE PLUMBING PLANS FOR THE ALTERED |
| | TOILET ROOM IN COMPLIANCE WITH SECTIONS 107.2.1 AND |
| | 107.3.5.3.1 WPB, AND FBC- 2020 PLUMBING. PROVIDE THE |
| | FOLLOWING LIST OF ITEMS: |
| | |
| | A) SANITARY DRAINAGE AND WATER RISER DRAWINGS. |
| | |
| | B) PLUMBING FLOOR PLAN LAYOUT DRAWING. |
| | |
| | C) PLUMBING FIXTURE SCHEDULE. |
| | |
| | 2) A-1: THE PROPOSED PROJECT SHALL BE IN COMPLIANCE |
| | WITH THE FBC-2020 EXISTING BUILDING CODE. PLEASE REFER |
| | TO SECTION 301.1 AND INDICATE WHICH COMPLIANCE METHOD |
| | WILL BE USED- PRESCRIPTIVE, WORK AREA, OR PERFORMANCE. |
| | A COMPLETE REVIEW CANNOT BE COMPLETED UNTIL A METHOD IS |
| | CHOSEN AND PLANS ARE REVISED IN ACCORDANCE WITH THE |
| | COMPLIANCE METHOD. |
| | |
| | 3) A-1: THE CURRENT TOILET ROOM DESIGN IS INCOMPLETE |
| | AND NOT IN COMPLIANCE WITH THE FBC- 2020 ACCESSIBILITY |
| | CODE. REFER TO SECTIONS 202.3, 213.1, AND 213.3.1 FBC |
| | ACC AND PROVIDE ENLARGED TOILET ROOM DRAWINGS SHOWING |
| | COMPLIANCE WITH THE FOLLOWING ITEMS- FBC ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSET- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORY- SECTION 606.2. |
| | C) TURNING SPACE DIAMETER- SECTION 304.3. |
| | D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| | SECTION 604.2. |
| | E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOOR- SECTION 604.4. |
| | F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | REFLECTIVE SURFACE- SECTION 603.3 |
| | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604. |
| | H) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION |
| | 604.6. |
| | I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| | 606.2. |
| | |
| | 4) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |