| Date |
Text |
| 2021-04-15 09:30:02 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY, THURSDAY & FRIDAY 7:00 AM TO 3:00 |
| | PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1 FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL16709-R7 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: COVER SHEET |
| | (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE (CODE |
| | VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| | INFORMATION ABOUT THE PRODUCT). EVALUATION REPORT PAGES |
| | 1-4 TO INCLUDE LIMITATIONS PAGE(S). |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL16709-R7 COVERS MULTIPLE ROOF SYSTEM TYPES |
| | A-2 THROUGH E, NO. W-1 THRU W-5. PLEASE SELECT SYSTEM |
| | NO.; EXPOSURE; ENCLOSURE; ROOF HEIGHT; ZONE AND |
| | ULTIMATE WIND SPEED. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING |
| | 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL12328-R9 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: COVER SHEET |
| | (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| | VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| | INFORMATION ABOUT THE PRODUCT). |
| | 4. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| | CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| | HIP & RIDGE METAL TO BE USED. |
| | 5. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| | DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| | CLEARLY IDENTIFIED ON DRAWING. |
| | |