| 2021-07-23 09:24:35 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT-21031169 |
| | 7/23/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. NEW PLANS HAVE BEEN |
| | SUBMITTED BY A NEW DESIGN PROFESSIONAL. 1ST REVIEW OF |
| | NEW PLAN COMMENTS BELOW. |
| | |
| | 1) SHEET P-201: THE NEW SANITARY DOES NOT SHOW PROPER |
| | VENTING OF THE NEW BATHROOM FIXTURES. THE DRAWING SHOWS |
| | TWO BATHROOM BRANCH DRAINS CONNECTING AT THE BASE OF A |
| | SOIL STACK. NO INDIVIDUAL OR COMMON VENTS FOR FIXTURE |
| | DRAINS, OR TYPICAL HORIZONTAL WET VENTING SYSTEMS ARE |
| | SHOWN. PLEASE REVIEW SECTIONS P3106, P3107, AND P3108 |
| | FBC RES. AND CORRECT THE PLAN AND ISOMETRIC DRAWING. |
| | |
| | 2) P-201 SHOWER PAN DETAIL: A) CORRECT THE 1/8 INCH |
| | SHOWER SLOPE SHOWN IN THE DETAIL TO INDICATE THE |
| | FINISHED FLOOR SLOPE SHALL NOT BE LESS THAN 1/4 INCH |
| | PER FT. AND NOT MORE THAN 1/2 INCH PER FT. PER SECTION |
| | P2709.1 FBC P. B) MISSING FROM THE DETAIL IS THE |
| | REQUIRED SHOWER PAN LINER- SECTIONS P2709.2- P2709.3.1 |
| | FBC P. C) A FLOOR DRAIN IS NOT AN APPROVED SHOWER |
| | RECEPTOR- SECTIONS P2709.4 FBC P. |
| | |
| | 3) P-201: PLEASE ADD A NOTE TO THE SLAB REPAIR DETAIL |
| | INDICATING THE EXPOSED SOIL WILL BE TERMITE TREATED- |
| | SECTION R318 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |