| Plan Review Notes For Permit 21031167 |
| Permit Number |
21031167 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-07-23 14:01:29 | 3RD REVIEW FBC-2020 RES. FUEL GAS | | | PERMIT- 21031167 | | | 7/23/2021 | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE REVISED DRAWING IS INDICATING A 795,000 TOTAL | | | BTU LOAD AT A TOTAL DEVELOPED LENGTH OF 49 FT. FROM | | | METER TO MOST REMOTE OUTLET. BASED ON THE SUBMITTED | | | SIZING TABLE 402.4(2) FBC FG, THE 1-1/4 IN. SCHED. 40 | | | PIPE IS UNDERSIZED AND WILL PROVIDE A MAXIMUM 583,000 | | | BTUS. A MINIMUM 1-1/2 IN. PIPE IS REQUIRED- SECTIONS- | | | G2412.4 & G2413.4.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|