| 2021-06-30 07:50:10 | 2ND REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 21031167 |
| | 6/30/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS NOT ADDRESSED |
| | FROM THE 1ST REVIEW ARE LISTED BELOW. |
| | |
| | 1B) DELIVERY PRESSURE AT THE METER. (NOT PROVIDED). |
| | |
| | 1K) PIPE SIZING TABLES. (LOW PRESSURE SCHED-40 |
| | GALVANIZED TABLE NOT PROVIDED). |
| | |
| | PLEASE NOTE TABLE 402.4(21) WAS SUBMITTED FOR LOW |
| | PRESSURE PE PIPING. THE DRAWING SHOWS A NEW TEE AT THE |
| | METER WHICH APPEARS TO INDICATE A 3/4- INCH MAIN PIPE. |
| | USING THE RELATIVE TABLE FOR LOW PRESSURE SCHED-40 |
| | GALVANIZED -TABLE G2413.4(1) [402.4(2) , THE 3/4- INCH |
| | INCH MAIN PIPE AT THE METER IS UNDERSIZED FOR THE |
| | INCREASED TOTAL BTU LOAD OF 795,000 AT A TOTAL |
| | DEVELOPED LENGTH OF 49 FT- SECTIONS G2413.1 & G2413.4.1 |
| | FBC RES, |
| | |
| | 3) SURVEY: PLEASE INDICATE THE REQUIRED 10 FT. |
| | CLEARANCE FOR THE GENERATOR EXHAUST TO WINDOW AND DOOR |
| | OPENINGS INTO THE BUILDING- SECTION R303.5.1 FBC RES. |
| | NEW COMMENT. |
| | 1) THE PRINTED NAME, SIGNATURE AND LICENSE NUMBER OF |
| | THE CONTRACTOR OR QUALIFIER SHALL BE PROVIDED ON THE |
| | GAS RISER DRAWING- SECTION 107.2.1 WPB, AND FLORIDA |
| | STATUTES 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |