| Plan Review Notes For Permit 21031163 |
| Permit Number |
21031163 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-28 09:47:44 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A GENERATOR PAD DRAWING WITH ANCHORING | | | DETAILS. IF A PREFABRICATED GENERATOR PAD IS TO BE | | | USED, SUBMIT SIGNED AND SEALED PAD DRAWINGS FROM A | | | FLORIDA LISENCED DESIGN PROFESSIONAL. FBC 107.2.1 | | | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS. | | | |
|