| Plan Review Notes For Permit 21031135 |
| Permit Number |
21031135 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-30 11:06:18 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | KITCHEN COUNTER OUTLETS DO NOT LOOK LIKE THEY WILL MEET | | | THE SPACING REQUIREMENTS IN 210.52. | | | | | | THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER SPACE | | | STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO | | | THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 | | | INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET | | | IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS | | | CODE IN SOME AREAS. PROVIDE CORRECTION. NEC | | | 210.52(C)(1) |
|