| 2021-04-20 07:48:16 | PLAN REVIEW / FUEL GAS |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: |
| | PROVISO: A SEPERATE GAS PERMIT IS REQUIRED FOR THE |
| | GENERATOR. PROVISO ON PLAN PAGE P-1.03. |
| | |
| | 1. SUBMIT GAS SIZING TABLES FOR POLYETHYLENE PLASTIC |
| | PIPING. |
| | G2413.3 (402.3)SIZING AND G2413.4 (402.4)SIZING TABLES |
| | AND EQUATIONS. |
| | |
| | 2. PROVIDE LENGTH OF 1 1/2" SCH 40 PIPE FROM METER TO |
| | FIRST TEE. |
| | G2413.4.1, G2413.4.2. AND . 402.4.1, 402.4.2. |
| | |
| | 3. SUBMIT MANUFACTURERS SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| | 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| | |
| | 4. SUBMIT GAS REGULATOR SPECIFICATIONS. 2017 FBC FUEL |
| | GAS SEC.305.1 OR 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| | |
| | NOTICE: REGULATORS SHALL HAVE A UNION INSTALLED WITHIN |
| | 1 FOOT OF EITHER SIDE OF THE REGULATOR FBC FG 410.2 |
| | |
| | NOTICE: REGULATORS SHALL BE LOCATED PER 409.1.3. |
| | |
| | NOTICE: HOOD FOR KITCHEN GAS GRILL SHALL COMPLY WITH |
| | 623.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |