| Plan Review Notes For Permit 21031098 |
| Permit Number |
21031098 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-29 13:14:54 | COMMERCIAL UNIT REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE UNIT USE (OCCUPANCY CLASSIFICATION) | | | PER FBC CHAPTER 3 | | | 2) PLEASE SHOW THE PREVIOUS USE ON THE DRAWINGS. | | | 3) DESIGNER NEEDS TO SIGN THE DRAWINGS - ALL | | | INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 |
|