| 2021-04-15 16:59:49 | PLAN REVIEW GENERATOR / FUEL GAS |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | |
| | 1)PROVIDE A GAS ISOMETRIC DRAWING: |
| | 1A) PROVIDE AN ISO DRAWING SHOWING THE ENTIRE SYSTEM |
| | INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST |
| | REMOTE OUTLET. THE BTUH LOAD OF EACH EXISTING APPLIANCE |
| | AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON |
| | THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. |
| | 1B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| | FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH |
| | LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & |
| | G2413.4.3. PROVIDED |
| | 1B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE |
| | OUTLET OF THE REGULATOR- SECTION G2421.1 |
| | 1C) PROVIDE THE BTUH LOAD OF THE GENERATOR. G2413.2 FBC |
| | RES. |
| | 1D) ) PROVIDE THE PIPE SIZING TABLES FOR EACH TYPE OF |
| | PIPING INSTALLED. G2413.2 FBC RES. |
| | |
| | REF: PLAN PAGE E1 FOR THE FOLLOWING: |
| | |
| | 2) THE GENERATOR SHALL NOT BE CLOSER THAN 10 FEET TO |
| | ANY BUILDING OPENING. |
| | R303.5.1 INTAKE OPENINGS: MECHANICAL AND GRAVITY |
| | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS |
| | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS |
| | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, |
| | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |