| 2021-05-05 13:45:27 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-21031014 |
| | 5/5/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1.1: THE REVISED P-1 RISER PLAN SHOWS A 1-1/2 |
| | IN.FIXTURE DRAIN WITH NO TRAP FOR THE ICE MAKER |
| | CONNECTING TO THE SANITARY STACK. CLARIFY IF THE DRAIN |
| | IS MAKING A DIRECT CONNECTION TO THE ICE MAKER OR IF AN |
| | INDIRECT CONNECTION IS BEING MADE USING A FLOOR DRAIN. |
| | PLEASE NOTE THAT FLOOR DRAINS SHALL HAVE A DRAIN OUTLET |
| | NOT LESS THAN 2 INCHES IN DIAMETER. IF A FLOOR DRAIN IS |
| | TO BE INSTALLED THE FLOOR MAY HAVE TO BE X-RAYED TO IN |
| | ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED |
| | FLOOR TENDONS. PLEASE PLACE A NOTE ON THE PLANS TO |
| | VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 2) P1.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING |
| | SLAB TO INSTALL A FLOOR DRAIN WILL REQUIRE FIRESTOPPING |
| | TO SEAL THE ANNULAR SPACE AROUND THE PIPING. IF |
| | APPLICABLE PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 |
| | FBC P, AND SECTION 714.4.1.2 FBC B. |
| | |
| | 3) P1.1: CLARIFY WHAT LIQUID IS BEING DRAINED FROM THE |
| | ICE MAKER- CONDENSATION FROM COOLING COILS OR ICE MELT |
| | DRAINAGE? PLEASE NOTE THAT CONDENSATION FROM COOLING |
| | COILS IS PROHIBITED FROM DRAINING INTO THE SANITARY |
| | SYSTEM PER SECTION 90-126 WPB CODE OF ORDINANCES. |
| | |
| | 4) P1.1: THE WATER RISER DOES NOT SHOW A SUPPLY |
| | CONNECTION TO THE NEW ICE MAKER. PLEASE SHOW THE |
| | CONNECTION AND REQUIRED DEVICES- WATER HAMMER ARRESTORS |
| | AND BACKFLOW PREVENTER- SECTION 604.9 AND 608.3 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| 2021-05-05 13:44:36 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-21031014 |
| | 5/5/2021 |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | PLAN REVIEW RESULTS: DENIED. |
| | 1) SHEET P1.1: THE REVISED P-1 RISER PLAN SHOWS A 1-1/2 |
| | IN.FIXTURE DRAIN WITH NO TRAP FOR THE ICE MAKER |
| | CONNECTING TO THE SANITARY STACK. CLARIFY IF THE DRAIN |
| | IS MAKING A DIRECT CONNECTION TO THE ICE MAKER OR IF AN |
| | INDIRECT CONNECTION IS BEING MADE USING A FLOOR DRAIN. |
| | PLEASE NOTE THAT FLOOR DRAINS SHALL HAVE A DRAIN OUTLET |
| | NOT LESS THAN 2 INCHES IN DIAMETER. IF A FLOOR DRAIN IS |
| | TO BE INSTALLED THE FLOOR MAY HAVE TO BE X-RAYED TO IN |
| | ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED |
| | FLOOR TENDONS. PLEASE PLACE A NOTE ON THE PLANS TO |
| | VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1 WPB. |
| | 2) P1.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING |
| | SLAB TO INSTALL A FLOOR DRAIN WILL REQUIRE FIRESTOPPING |
| | TO SEAL THE ANNULAR SPACE AROUND THE PIPING. IF |
| | APPLICABLE PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 |
| | FBC P, AND SECTION 714.4.1.2 FBC B. |
| | 3) P1.1: CLARIFY WHAT LIQUID IS BEING DRAINED FROM THE |
| | ICE MAKER- CONDENSATION FROM COOLING COILS OR ICE MELT |
| | DRAINAGE? PLEASE NOTE THAT CONDENSATION FROM COOLING |
| | COILS IS PROHIBITED FROM DRAINING INTO THE SANITARY |
| | SYSTEM PER SECTION 90-126 WPB CODE OF ORDINANCES. |
| | 4) P1.1: THE WATER RISER DOES NOT SHOW A SUPPLY |
| | CONNECTION TO THE NEW ICE MAKER. PLEASE SHOW THE |
| | CONNECTION AND REQUIRED DEVICES- WATER HAMMER ARRESTORS |
| | AND BACKFLOW PREVENTER- SECTION 604.9 AND 608.3 FBC P. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |