| 2021-03-29 17:48:45 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21031014 |
| | ADD: 1200 S. FLAGLER DR. # PH-4 |
| | CONT: CAMBRIDGE CONSTRUCTION LLC |
| | TEL: 561-784-3722 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: ON. MARCH 29TH/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) THE COVER SHEET UNDER THE HEADING PROJECT DATA: |
| | |
| | 1A) THE LIST OF CODES THIS PLAN WAS DEVELOPED WAS THE |
| | 2017 FLORIDA FAMILY OF CODES. PLEASE BE AWARE THE 2020 |
| | FLORIDA FAMILY OF CODES WAS ADOPTED STATEWIDE ON DEC. |
| | 31/ 2020. PLEASE UPDATE YOUR PLANS. |
| | |
| | 1B) UNDER THE HEADING THE CONSTRUCTION TYPE LISTED IS |
| | V-B UN-PROTECTED, UN-SPRINKLERED MAIN HOUSE. PLEASE |
| | UPDATE PLANS UNDER THE 2020 FLORIDA BUILDING CODE 7TH |
| | EDITION THIS BUILDING IS CONSIDERED A HIGHRISE AND |
| | CONSTRUCTION TYPE I-A, SPRINKLERED. |
| | |
| | |
| | 2) DEMOLITION PLAN. THE FLOOR PLAN INDICATES STRUCTURAL |
| | WORK ON THE BALCONY SLABS, CONCRETE AND STEEL COLUMN |
| | REPAIR WITH TRIANON CONDOMINIUM ASSOCIATION. PLEASE |
| | NOTE THIS WORK WOULD BE UNDER A SEPARATE PERMIT, REVIEW |
| | WITH ASSOCIATED FEES. THIS BUILDING IS A THRESHOLD |
| | BUILDING AND REQUIRE THRESHOLD DOCUMENTS/ FORMS |
| | SUBMITTED WITH CONCRETE REPAIR PERMIT. |
| | |
| | 3) SHEET DOORS & FINISH SCHEDULES. THE FINISH SCHEDULE |
| | FOR THE FLOORS INDICATES WOOD FLOORING WHEREAS THE |
| | FLOOR INSULATION SUBMITTED WHISPER MAT CS IS FOR |
| | PORCELAIN TILE NOT WOOD. FLOOR INSULATION (FBC-B 2020) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |