| 2021-03-24 16:06:35 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) FBC B 107.2, THE IMAGES SUBMITTED UNDER THE TITLE | | | FORM 100 MAIN HOUSE APPEAR TO SHOW MORE THAN (1) | | | STRUCTURE WITH INDICATIONS OF BEING PART OF THIS PERMIT | | | WHILE THE APPLICATION INDICATES MAIN HOUSE ONLY. PLEASE | | | CLARIFY THE PROPOSED WORK. | | | | | | 2) FBC B 107.2, THE SUBMITTED SPECIFICATIONS FOR SNAP | | | MAX FROM EXTREME METAL FABRICATORS METHOD "A" DOES NOT | | | SHOW A RATING FOR 170 MPH (ZONE 3) WITHIN THE PROVIDED | | | TABLES. PLEASE PROVIDE ANOTHER METHOD TO MEET THE | | | WINDLOAD REQUIREMENTS FOR ZONE 3. |
|