| Plan Review Notes For Permit 21030940 |
| Permit Number |
21030940 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-29 14:55:12 | R2 UNIT PARTIAL DEMO | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW HOW THE ELEVATOR HOISTWAY WILL REMAIN | | | FIRE PROTECTED PER FBC 3006.3 HOISTWAY OPENING | | | PROTECTION. | | | WHERE SECTION 3006.2 REQUIRES PROTECTION OF THE | | | ELEVATOR HOISTWAY DOOR OPENING, THE PROTECTION SHALL BE | | | PROVIDED BY ONE OF THE FOLLOWING: SEE 3006.3 | | | 2) CONSTRUCTION TYPE SHOWN ON THE DRAWINGS IS | | | INCORRECT. FBC CHAPTER 6 |
|