2021-04-23 15:21:041ST REVIEW FBC-2020 MECHANICAL
 PERMIT- 21030933 2ND CYCLE
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.2: OUTDOOR AIR CALCULATIONS: PLEASE PROVIDE
 OUTDOOR AIR CALCULATIONS FOR EACH SPACE USING FBC M
 403.3.1.1 WHICH STATES THE ARCHITECTURAL OCCUPANT COUNT
 MUST NOT BE USED. TABLE 403.3.1.1 MUST BE USED FOR EACH
 USE OF SPACE. PICK AN OCCUPANCY CLASSIFICATION WHICH
 MOST CLOSELY RELATES TO YOUR USE OF SPACE, IDENTIFY IT
 ON YOUR CALCULATIONS AND DO THE MATH FROM THE COLUMNS
 TO THE RIGHT. IF THE CALCULATIONS ARE WORKED USING THIS
 METHOD THE CALCULATIONS PRESENTED IN THIS SUBMITTAL IS
 UNDER SIZED. IF YOU NEED ASSISTANCE WITH CALCULATING
 USING THE TABLE INSTEAD OF THE ARCHITECTURAL OCCUPANT
 LOAD PLEASE CALL ME.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  