2021-04-02 16:39:0604/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET GI0.1;
 A. PLEASE PROVIDE THE APPLICABLE CODE AND VOLUME BEING
 USED PER THE WPB AMENDMENTS TO THE FBC SEC. 102.3
 APPLICATION OF REFERENCES.
  
 B. PLEASE PROVIDE WHAT TYPE OF OCCUPANCY THIS INTERIOR
 BUILD-OUT WILL BE AND THE OCCUPANCY LOAD WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. PLEASE GIVE THE LEVEL OF ALTERATION PER 2020 FLORIDA
 EXISTING BUILDING CODE 301.1.
  
 IT IS NOTED THAT ON ALS1.0 SOME OF THIS INFORMATION IS
 THERE BUT PLEASE COPY TO THIS PAGE AND PLUMBING IF
 POSSIBLE BUT NOT NECESSARY.
  
 2. ON SHEET ALS0.1;
 3. SOME OF THESE COMMENTS MAY BE IN A4.0, BUT THEY ARE
 NOT CONSISTENT OR REFERENCED TO EACH OTHER. YOU MAY
 CHOOSE TO COMBINE OR CORRECT.
  
 A. ON DETAIL NINE, PLEASE SHOW THE MIRROR DIMENSIONS OF
 40" TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC.
 603.3.
  
 B. PLEASE SHOW THE DIMENSION OF THE TOILET 17" INCHES
 TO 19" INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT
 PER THE 2020 FBC ACC SEC. 604.4 SEATS.
  
 C. GRAB BARS ON THE HORIZONTAL NEED TO BE MEASURED
 CENTER TO CENTER PER THE 2020 FBC SEC. 604.5.2 REAR
 WALL. PLEASE ALSO SHOW THE SIDE WALL PER THE 2020 FBC
 SEC. 604.5.1 SIDE WALL.
  
 D. PROVIDE DRAWINGS AND DETAILS SHOWING: A) THE 30 X 48
 IN. CLEAR FLOOR SPACE FOR A FORWARD APPROACH TO THE
 WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN 2020 FBC ACC
 SEC. 602.2 CLEAR FLOOR SPACE AND PLEASE SHOW KNEE AND
 TOE CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS PER THE
 2020 FBC ACC SEC. 306, 307, & 602.2, COMPLIANCE WITH
 2020 FBC ACC SEC. 307.2 PROTRUSION LIMITS.
  
 E. PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES ON
 LAVS, URINAL, SINKS TOILETS, AND DRINKING FOUNTAIN PER
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
  
 F. PLEASE SHOW DETAILS OF THE BACKING FOR GRAB BARS
 REINFORCEMENT THAT MUST BE SUFFICIENT TO PERMIT THE
 INSTALLATION OF REAR AND SIDE WALL GRAB BARS THAT FULLY
 MEET ALL ACCESSIBILITY REQUIREMENTS, INCLUDING, BUT NOT
 LIMITED TO, REQUIRED LENGTH, INSTALLATION HEIGHT, AND
 STRUCTURAL STRENGTH.
  
 G. DETAIL 10 HAS THE HORIZONTAL GRAB BARS TO THE EDGES
 OF THE DIMENSION, AND THEY NEED TO BE TO THE CENTER.
  
 IT IS NOTED THAT THE FBC ACC IS IN REFERENCE BUT CAN
 THE YEAR BE ADDED TO IT, PLEASE.
  
 4. ON SHEET A1.0;
 A. THE DRINKING FOUNTAIN IS IN A BREAK ROOM THAT IS NOT
 CLEAR IF THE BREAK ROOM IS FOR PATIENTS. IF SO, PLEASE
 PROVIDE SIGN-AGE TO THE DRINKING FOUNTAIN LOCATION
 SOMEWHERE IN THE LOBBY PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. PLEASE SHOW ALL ACCESSIBLE, CLEAR FLOOR SPACE FOR
 FIXTURE CLEARANCES PER FLORIDA BUILDING CODE AND
 FLORIDA ACCESSIBILITY CODE.
  
 C. PLEASE CLEARLY SHOW THE COOLER ON THE PLANS AND
 ACCESSIBILITY REQUIREMENTS INCLUDING CLEAR FLOOR SPACE
 APPROACH AND REACH RANGES TO CONTROLS 2017 FBC ACC SEC.
 305 & 308.
  
 D. AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH
 TYPE PROVIDED IN EACH ACCESSIBLE ROOM PER THE 2020 FBC
 ACC SEC. 212.3 SINKS.
  
 5. ON SHEET A4.0;
 A. DETAIL A, THE DOOR SWING INTO THE CLEAR FLOOR SPACE
 OR CLEARANCE OF 30? X 48? PER THE 2020 FBC-ACC SEC.
 604.8.1.2.
  
 B. ELEMENTS ARE MISSING IS MANY DETAILS AND DIMENSION;
 FOR EXAMPLE, THE MIRROR INS THE ACCESSIBLE COMPARTMENT
 NOT SHOW AND NO DIMENSION FOR THE LAV ON IN THE OPEN
 AREA, THE GRAB BARS HAVE NO DIMENSIONS.
  
 C. THE TOILET SHOWS A DIMENSION OF 1"-6" AND NEEDS TO
 ADD THE 1" -8" MAX PER THE 202 FBC ACC SEC. 604.2.
  
 D. DOOR HANDLES HARDWARE SHOULD BE NOTED ON BOTH SIDES
 OF THE DOOR PER THE 2017 FBC ACC SEC. 404.2.7.
  
 E. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 F. PLEASE SHOW CLEAR FLOOR SPACE FOR URINAL PER THE
 2020 FBC-ACC SEC. 604.8.1.2.
  
 G. ON DETAIL TWO, THE TOILET HANDLE ON THE WRONG SIDE,
 2020 FBC ACC 604.6.
  
 H. PLEASE SHOW THE CLEAR FLOOR SPACE DIMENSION FOR BOTH
 RESTS ROOMS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 I. ON DETAIL D, PLEASE SHOW THE CLEAR FLOOR SPACE FOR
 THE BREAK-ROOM PER THE 2017 FBC ACC SEC. 602.
  
 J. SEAT NEEDS TO BE OPEN FRONT, 2017 FBC P 420.3 WATER
 CLOSET SEATS.
  
 6. ON SHEET A4.3;
 A. THE TOILET SHOWS A DIMENSION OF 1"-6" AND NEEDS TO
 ADD THE 1" -8" MAX PER THE 202 FBC ACC SEC. 604.2.
  
 B. PLEASE SHOW THE DIMENSION OF THE TOILET 17" INCHES
 TO 19" INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT
 PER THE 2020 FBC ACC SEC. 604.4 SEATS.
  
 C. PLEASE SHOE ALL ACCESSIBLE, CLEAR FLOOR SPACE FOR
 FIXTURE CLEARANCES PER FLORIDA BUILDING CODE AND
 FLORIDA ACCESSIBILITY CODE.
  
 D. PLEASE SHOW THE TURNING SPACE DIAMETER- SECTION
 304.3.
  
 E, PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE EXAM ROOM
 OF THE SINK PER THE 2020 FBC SEC. 602.
  
 7. ON SHEET P2.0;
 A. PLEASE PROVIDE A VENT BETWEEN MS1 AND FD PER THE
 2020 FBC SEC. 901.2.
  
 B. THE DRINKING FOUNTAIN NEEDS TO BE DOWNSTREAM OF THE
 WET VENT'S BATHROOM GROUPS PER THE 2020 FBC SEC. 912.1
 HORIZONTAL WET VENTS PERMITTED.
  
 C. PLEASE SHOW THE TRAP PRIMER FOR THE FLOOR DRAIN PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 8. ON SHEET P2.1;
 A. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES
 MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE
 REFER TO THE 2020 FBC ENERGY CODE TABLE C404.5.1.
  
 B. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 INLINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10.
  
 9. ON SHEET P3.0;
 A. THE RELIEF LINE SHALL TERMINATE IN THE PAN, AND THE
 PAN IN MOP SINK PET THE 2020 FBC SEC P FBC P 504.7.2.
  
 B. PLEASE PROVIDE DETAIL OF THE INSULATION TYPE FOR THE
 RECIRCULATION SYSTEM PER THE 2020 FBC CE 404.4. IF YOU
 LIKE TO SET UP A ZOOM MEETING, IF SOME OF THESE
 COMMENTS ARE NOT CLEAR, FEEL FREE TO-CONTACT ME. THANK
 YOU.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-67200
  
  