| Plan Review Notes For Permit 21030928 |
| Permit Number |
21030928 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-04-12 08:43:55 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) [NOT COMPLIED. SEPARATE THE SIZE OF THE DOOR FROM | | | THE SIDELITE. SPECIFY THE DOOR SIZE AND THE SIDELITE | | | SIZE.] SUBMIT A FLOOR PLAN THAT SHOWS THE LOCATION OF | | | THE DOOR AND SIDELITE. SPECIFY THE SIZE OF THE DOOR AND | | | THE SIZE OF THE SIDELITE ON THE PLAN. FBC AMENDMENTS | | | 107.2.1 | | | | | | 2) [NOT COMPLIED. C AND C PRESSURES NOT PROVIDED.] | | | SPECIFY THE REQUIRED COMPONENT AND CLADDING WIND LOAD | | | PRESSURES FOR THE DOOR AND SIDELITE ON THE PLANS. | | | FBC-R301 | | | | | | 3) [NOT COMPLIED. THE PRODUCT APPROVAL PROVIDED DOES | | | NOT REFERENCE THE 2020 FBC.] SUBMIT A PRODUCT APPROVAL | | | FOR THE DOOR/SIDELITE THAT HAS BEEN EVAULUATED TO | | | COMPLY WITH THE 2020 FBC, SEVENTH EDITION. FBC | | | AMENDMENTS 107.3.4 | | | | | | 4) [NOT COMPLIED. THE SPECIFIC DOOR AND SIDELITE SIZE | | | WAS NOT HI-LIGHTED OR CIRCLED.] CIRCLE OR HI-LIGHT THE | | | ITEMS ON THE PRODUCT APPROVAL SUCH AS THE DESIGN | | | PRESSURES THAT APPLY TO THIS PROJECT. FBC AMENDMENTS | | | 107.2.1 | | | | | | |
|