2021-04-07 08:21:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH FBC-R4501.17.1.4 WHERE THE
 BARRIER IS COMPOSED OF HORIZONTAL AND VERTICAL MEMBERS
 AND THE DISTANCE BETWEEN THE TOPS OF THE HORIZONTAL
 MEMBERS IS LESS THAN 45 INCHES (1143 MM), THE
 HORIZONTAL MEMBERS SHALL BE LOCATED ON THE SWIMMING
 POOL SIDE OF THE FENCE. SPACING BETWEEN VERTICAL
 MEMBERS SHALL NOT EXCEED 1-3/4 INCHES (44 MM) IN WIDTH.
 WHERE THERE ARE DECORATIVE CUTOUTS WITHIN VERTICAL
 MEMBERS, SPACING WITHIN THE CUTOUTS SHALL NOT EXCEED
 1-3/4 INCHES (44 MM) IN WIDTH.
  
 2) SHOW COMPLIANCE WITH FBC-R4501.17.1.8 ACCESS GATES,
 WHEN PROVIDED, SHALL BE SELF-CLOSING AND SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTIONS R4501.17.1.1 THROUGH
 R4501.17.1.7 AND SHALL BE EQUIPPED WITH A SELF-LATCHING
 LOCKING DEVICE LOCATED ON THE POOL SIDE OF THE GATE.
 WHERE THE DEVICE RELEASE IS LOCATED NO LESS THAN 54
 INCHES (1372 MM) FROM THE BOTTOM OF THE GATE, THE
 DEVICE RELEASE MECHANISM MAY BE LOCATED ON EITHER SIDE
 OF THE GATE AND SO PLACED THAT IT CANNOT BE REACHED BY
 A YOUNG CHILD OVER THE TOP OR THROUGH ANY OPENING OR
 GAP FROM THE OUTSIDE. GATES THAT PROVIDE ACCESS TO THE
 SWIMMING POOL MUST OPEN OUTWARD AWAY FROM THE POOL. THE
 GATES AND BARRIER SHALL HAVE NO OPENING GREATER THAN
 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457 MM) OF THE
 RELEASE MECHANISM.
  