Plan Review Notes
Plan Review Notes For Permit 21030892
Permit Number 21030892
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-08 17:30:331ST REVIEW FBC-2020 RES.
 PERMIT- 21030892
 4/8/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P2: PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE RANGE SHOWING THE BTU LOAD AND INPUT PRESSURE-
 SECTION G2447.1 FBC RES. PLEASE NOTE THAT THE SPECS AND
 INSTALL MANUAL MAY BE DEFERRED AND ONSITE AT TIME OF
 INSPECTION- SECTION 107.3.4.1 WPB.
  
 2) P2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SECTION- G2407.1 FBC RES.
  
 3) P2: UPDATE THE FBC- 2017 CODE REFERENCE IN NOTE #1.
 THE FBC-2020 7TH EDITION CODES WENT INTO EFFECT ON
 12/31/2020.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2021-04-08 17:29:531ST REVIEW FBC-2020 RES.
 PERMIT- 21030892
 4/8/2021
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
 1) P2: PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE RANGE SHOWING THE BTU LOAD AND INPUT PRESSURE-
 SECTION G2447.1 FBC RES. PLEASE NOTE THAT THE SPECS AND
 INSTALL MANUAL MAY BE DEFERRED AND ONSITE AT TIME OF
 INSPECTION- SECTION 107.3.4.1 WPB.
 2) P2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SECTION- G2407.1 FBC RES.
 3) P2: UPDATE THE FBC- 2017 CODE REFERENCE IN NOTE #1.
 THE FBC-2020 7TH EDITION CODES WENT INTO EFFECT ON
 12/31/2020.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  