| 2021-04-15 14:57:20 | SFR ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) NEW FREE STANDING GARAGE NEEDS TO BE ON A SEPARATE |
| | PERMIT - PLEASE ACKNOWLEDGE THIS ON THE DRAWING. |
| | 2) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS |
| | AND ROOFING SYSTEMS. |
| | 3) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| | APPROVED BY THE BUILDING DESIGNER OF RECORD OR THE |
| | PRODUCT APPROVAL NUMBERS NEED TO BE SHOWN ON THE |
| | DRAWINGS. |
| | 4) PLEASE SHOW ROOF DRAINAGE SYSTEM ON THE ROOF PLAN TO |
| | COMPLY WITH FBC R903.4 |
| | 5) PLEASE SHOW THE REQUIRED OVERFLOW SCUPPERS TO COMPLY |
| | WITH FBC R903.4.1 |
| | 6) PLEASE SHOW ROOF VENTILATION TO COMPLY WITH FBC |
| | R806.1 |
| | 7) PLEASE SHOW THE STEP RISER HEIGHT AND TREAD DEPTH TO |
| | COMPLY WITH FBC R311.7.5 |
| | 8) PLEASE SHOW TUB AND SHOWER WALL AREAS TO COMPLY WITH |
| | FBC R702.4.2 |
| | 9) ROOFING SYSTEMS AND WINDOW AND DOOR PRODUCT |
| | APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS |
| | TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - |
| | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |