| 2021-06-23 12:39:54 | 06/23/21 2 ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR |
| | THE MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM |
| | ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN |
| | DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER |
| | ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 |
| | EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE |
| | (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE |
| | DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE |
| | SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH |
| | CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS, |
| | INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES, |
| | HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS |
| | EXCEPT THE PUMP. |
| | |
| | 2. SECOND REQUEST; PLEASE SUBMIT THE POOL PUMP CURVE. |
| | IDENTIFY THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO |
| | THE PUMP BEING INSTALLED ON THIS POOL AND SHOW IT IN A |
| | BAR GRAPH. THIS IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM |
| | FLOW FROM THE TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 |
| | - 2013 SECS. 4.4.9, 4.4.9.1. |
| | |
| | 3. SECOND REQUEST; PLEASE PROVIDE THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PUMP, FILTER, CHLORINATOR, AND |
| | GAS HEATER PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 4. SECOND REQUEST; PLEASE PROVIDE DOCUMENTATION THAT |
| | THE GAS AND SPA HEATERS SHALL HAVE A MINIMUM THERMAL |
| | EFFICIENCY OF 82 % FOR HEATERS MANUFACTURED ON OR AFTER |
| | APRIL 16, 2013, WHEN TESTED IN ACCORDANCE WITH ANSI Z |
| | 21.56. POOL HEATERS FIRED BY NATURAL OR LP GAS SHALL |
| | NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS PER THE 2017 |
| | FBC-ENERGY ? SEC. R403.10.4. |
| | |
| | 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |