Plan Review Notes
Plan Review Notes For Permit 21030889
Permit Number 21030889
Review Stop P
Sequence Number 2
Notes
Date Text
2021-06-23 12:39:5406/23/21 2 ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2. SECOND REQUEST; PLEASE SUBMIT THE POOL PUMP CURVE.
 IDENTIFY THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO
 THE PUMP BEING INSTALLED ON THIS POOL AND SHOW IT IN A
 BAR GRAPH. THIS IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM
 FLOW FROM THE TDH CALCULATIONS PER THE ANSI/APSP/ICC 7
 - 2013 SECS. 4.4.9, 4.4.9.1.
  
 3. SECOND REQUEST; PLEASE PROVIDE THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PUMP, FILTER, CHLORINATOR, AND
 GAS HEATER PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 4. SECOND REQUEST; PLEASE PROVIDE DOCUMENTATION THAT
 THE GAS AND SPA HEATERS SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82 % FOR HEATERS MANUFACTURED ON OR AFTER
 APRIL 16, 2013, WHEN TESTED IN ACCORDANCE WITH ANSI Z
 21.56. POOL HEATERS FIRED BY NATURAL OR LP GAS SHALL
 NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS PER THE 2017
 FBC-ENERGY ? SEC. R403.10.4.
  
 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  