Date Text
2021-03-22 10:54:3703/22/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW
 THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS.
 THE CALCULATION SHOWS THE PIPE, FITTINGS, VALVES,
 FILTER, BUT THERE IS NO FRICTION LOSS ASSOCIATED HEATER
 AND CHLORINATOR PLEASE ADD THESE ITEMS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 3. PLEASE SUBMIT SPECIFICATION THE HEAT PUMP POOL
 HEATERS HAVE A MINIMUM COP OF 4.0 WHEN TESTED IN
 ACCORDANCE WITH AHRI 1160, TABLE 2, STANDARD RATING
 CONDITIONS - LOW AIR TEMPERATURE. A TEST REPORT FROM AN
 INDEPENDENT LABORATORY IS REQUIRED TO VERIFY PROCEDURE
 COMPLIANCE PER THE 2017 FBC-ENERGY SEC. R 403.10.5
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  