| 2021-05-26 14:10:20 | INTERIOR RENOVATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWINGS ADDED TO PROJECTDOX ON 5/19/2021 NEED TO BE | | | SIGNED AND SEALED BY THE DESIGNER. (DRAWING A1.0 AND | | | CURB DETAIL 1 AND 2) FBC 107.1 | | | DRAWINGS ADDED TO PROJECTDOX ON 5/19/2021 = SIGNED AND | | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | | DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL |
|