| Plan Review Notes For Permit 21030845 |
| Permit Number |
21030845 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-19 08:05:37 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21030845 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A1.0: THE NEW WALK-IN REF. SHOWN ON THIS SHEET | | | SHALL REQUIRE A SEPARATE SUBMITTAL WITH A PERMIT AND | | | REVIEW. PLEASE PROVIDE A STATEMENT ON THE PLANS | | | REFLECTING THIS. | | | | | | 2) SHEET M2.0: PLEASE PROVIDE THE OUTDOOR AIR | | | CALCULATIONS BASED ON THE 2020 FBC M SECTION 403.3.1.1 | | | AND TABLE 403.3.1.1. PLEASE USE THESE TWO SECTIONS TO | | | CALCULATE THE REQUIRED OUTDOOR AIR FOR THE USE OF THIS | | | SPACE, NOT THE ARCHITECT OCCUPANT COUNT. (EXAMPLE) THE | | | FLORIST AREA APPEARS TO BE A SALES AREA. THIS WOULD BE | | | FIGURED BY USING THE (RETAIL STORES, SALES FLOORS AND | | | SHOWROOM FLOORS). | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|