| 2021-04-13 09:24:52 | COMMERCIAL BUILDING INTERIOR ALT |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE PROVIDE ROOF TOP AC CURB OR STAND MOUNTING |
| | DETAILS TO COMPLY WITH FBC 1510.10 MECHANICAL UNITS. |
| | ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS |
| | RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF |
| | SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE |
| | UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM |
| | CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10. |
| | 2) PLEASE PROVIDE A STATEMENT FROM THE ARCHITECT OR |
| | ENGINEER TO ADDRESS THE ADDITIONAL WEIGHT OF THE ADDED |
| | AC SYSTEM ON THE ROOF - FBC E707.2 ADDITION OR |
| | REPLACEMENT OF ROOFING OR REPLACEMENT OF EQUIPMENT. |
| | WHERE ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT |
| | OF EQUIPMENT RESULTS IN ADDITIONAL DEAD LOADS, |
| | STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING OR |
| | EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | 3) PLEASE PROVIDE A ROOF PLAN SHOWING THE LOCATION OF |
| | THE ADDED MECHANICAL EQUIPMENT AND GUARDS IF REQUIRED |
| | FBC 1015.6 MECHANICAL EQUIPMENT, SYSTEMS AND DEVICES. |
| | GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. |
| | |
| | |