| 2021-04-06 07:45:58 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) PROVIDE DRAINAGE/WATER RUN OFF INDICATORS SHOWING | | | WATER SHED AWAY FROM DEN ON SURVEY/SITE PLAN APPROVED | | | BY SURVEYOR. | | | | | | 2) PROVIDE DIMENSIONS OF EXISTING PERIMETER | | | FOOTING/THICKENED EDGE OF SLAB. | | | | | | 3) PROVIDE INFORMATION OF EXISTING DOORS | | | (SCREEN/SOLID?). | | | | | | 4) RE-EVALUATE THE ENERGY EFFICIENCY CODE FOR BUILDING | | | CONSTRUCTION BY INCLUDING THE GLAZED WALL, DOOR & | | | WINDOW AREAS. | | | | | | |
|