| Notes |
| Date |
Text |
| 2021-04-22 09:29:27 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A DIMENSIONED DRAWING OF THE STOREFRONT LIKE | | | THE ONE THAT WAS CROSSED OUT ON THE CONTRACT. FBC | | | AMENDMENTS107.2.1 | | | | | | 2) SPECIFY THE REQUIRED WIND LOAD PRESSURES FOR THIS | | | STOREFRONT DOOR OPENING IN 170 MPH VULT EXPOSURE C. FBC | | | BUILDING SECTION 1609 | | | | | | 3) CIRCLE OR HI-LIGHT THE ITEMS LISTED IN THE PRODUCT | | | APPROVAL (INCLUDING THE DESIGN PRESSURES) THAT APPLY TO | | | THIS PROJECT. FBC AMENDMENTS107.2.1 | | | | | | | | | | | | |
|