| Date |
Text |
| 2021-03-29 15:45:47 | 03/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A1.1.1, PLEASE GIVE ALL DIMENSIONS FOR |
| | FIXTURE CLEARANCES PER THE FLORIDA BUILDING CODE AND |
| | FLORIDA ACCESSIBILITY CODE. |
| | |
| | 2. ON SHEET A9.0.1, 7; |
| | |
| | A. PLEASE SHOW THE WATER CLOSET FLUSH CONTROL LOCATION |
| | PER THE 2020 FBC SEC. 604.6 FLUSH CONTROLS. |
| | |
| | B. PLEASE THE REFLECTIVE PART OF THE MIRROR NEEDS TO BE |
| | 40? TO THE REFLECTIVE SIDE PER THE 2017 FBC ACC SEC. |
| | 603.3. |
| | |
| | C. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5. |
| | |
| | D. PLEASE SHOW THE REAR AND SIDE DIMENSIONS FOR GRAB |
| | BARS PER THE 2020 FBC ACC SEC. 604.5. |
| | |
| | E. PLEASE PROVIDE THE KNEE AND TOE CLEARANCES FOR THE |
| | LAVATORY PER THE 2020 FBC ACC SEC. 306.3 TOE CLEARANCE. |
| | |
| | F. ON DETAIL B, IT SHOWS 1?- 6? MAXIMUM, AND PLEASE ADD |
| | THE TO THE CENTERLINE OF THE WATER CLOSET SHALL BE |
| | 1?-4? INCHES MINIMUM FROM THE SIDEWALL PER THE 2020 FBC |
| | ACC. 604.2. |
| | |
| | G. THE TOILET SEATS NEED TO BE 17? INCHES TO 19? INCHES |
| | MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2020 |
| | FBC ACC SEC. 604.4 SEATS. |
| | |
| | 3. THE WASHER IS CONSIDERED FOR COMMERCIAL USE AND WILL |
| | REQUIRE A LINT INTERCEPTOR. PLEASE SHOW AND PROVIDE |
| | SPECIFICATION SUPPLY DETAILS OR NOTES PER THE 2020 FBC |
| | SEC. 1003.6. |
| | |
| | 4. ON SHEET P0.1; |
| | A. THE ICE MAKER AND COFFEE MAKER SHALL BE EQUIPPED |
| | WITH AN INLINE VACUUM BREAKER THAT COMPLIES WITH ASSE |
| | 1024 PER THE 2020 FBC ACC SEC. 608.13.10. |
| | |
| | B. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES |
| | MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE |
| | REFER TO THE 2020 FBC ENERGY CODE TABLE C404.5.1. |
| | |
| | 5. ON SHEET P3.1, WASHING MACHINE VALVES MUST BE |
| | ACCESSIBLE FOR SHUTTING OFF WITHOUT MOVING UNITS, 2020 |
| | FBC P 604.10.3 ACCESS. ACCESSIBLE SIGNIFIES ACCESS THAT |
| | REQUIRES THE REMOVAL OF AN ACCESS PANEL OR SIMILAR |
| | REMOVABLE OBSTRUCTION. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |