| Plan Review Notes For Permit 21030764 |
| Permit Number |
21030764 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-05-07 06:36:49 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21030764 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR BOTH THE | | | OFFICE AREAS AND THE CONFERENCE ROOM. PLEASE SEE | | | SECTION 403.3.1.1 ( CANNOT USE ARCHITECTURAL OCCUPANT | | | LOAD FOR THIS CALCULATION). PLEASE SEE TABLE 403.3.1.1 | | | FOR OFFICE AND CONFERENCE ROOMS TO COMPUTE THE | | | CALCULATIONS FOR THE OUTDOOR AIR. IF YOU HAVE ANY | | | QUESTIONS PLEASE DON?T HESITATE TO CALL ME. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|