Plan Review Notes
Plan Review Notes For Permit 21030764
Permit Number 21030764
Review Stop M
Sequence Number 2
Notes
Date Text
2021-05-07 06:36:492ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21030764
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR BOTH THE
 OFFICE AREAS AND THE CONFERENCE ROOM. PLEASE SEE
 SECTION 403.3.1.1 ( CANNOT USE ARCHITECTURAL OCCUPANT
 LOAD FOR THIS CALCULATION). PLEASE SEE TABLE 403.3.1.1
 FOR OFFICE AND CONFERENCE ROOMS TO COMPUTE THE
 CALCULATIONS FOR THE OUTDOOR AIR. IF YOU HAVE ANY
 QUESTIONS PLEASE DON?T HESITATE TO CALL ME.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  