Plan Review Notes
Plan Review Notes For Permit 21030748
Permit Number 21030748
Review Stop M
Sequence Number 1
Notes
Date Text
2021-04-14 15:12:46PLAN DENIED
 1) PROVIDE FRESH AIR CALCULATIONS PRE
 TABLE 403.3.1.1 MINIMUM VENTILATION RATES
 2020FBC (M)
 2) HOW ARE YOU GOING TO CONTROL THE TEMPERATURE
 IN CORRIDOR # 110