| 2021-03-30 14:27:01 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21030687 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE |
| | OF SPACE ACCORDING TO TABLE 403.3.1.1 I.E. OFFICE |
| | SPACE, CONFERENCE ROOM, BREAKROOM. PLEASE BREAK THE |
| | OUTDOOR AIR DOWN TO EACH MECHANICAL SYSTEM ACCORDING TO |
| | THE SPACE BEING CONDITIONED. FBC M 403.3.1.1 |
| | |
| | 2) THE AIR SYSTEM SIZING SUMMARY IS FOR AHU-1 ONLY |
| | PLEASE SUBMIT AN EQUIPMENT SIZING CALCULATION FOR EACH |
| | MECHANICAL SYSTEM IN THIS TENANT SPACE. FBC EC C403.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |