| 2021-05-06 16:56:57 | 3RD REVIEW FBC-2020 RES. |
| | PERMIT- 21030608 |
| | 5/6/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | NFPA- 58 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE CLARIFY WHICH LP GAS REGULATORS WILL BE |
| | INSTALLED AT THE TANK AND AT THE SERVICE ENTRANCE TO |
| | THE HOUSE. THE MAKE AND MODEL SELECTIONS SHOWN ON THE |
| | RISER DRAWINGS BY ROBERT PETTET AND JERIMIAH CAY DO NOT |
| | MATCH- SECTION 107.2.1 WPB. |
| | |
| | 2) JERIMIAH CAY RISER: |
| | A) THE 1/2 IN. SCHEDULE 40 GAS PIPING SUPPLYING THE |
| | COOKTOP AND FIREPLACE IS UNDERSIZED-. A MIN 3/4 IN. |
| | PIPE IS REQUIRED BASED ON THE SIZING TABLE YOU HAVE |
| | SELECTED- TABLE 402.4(28) FBC FG. |
| | B) 2ND REQUEST: PLEASE PROVIDE THE EHD OF THE 3/4 IN. |
| | CSST BASED ON THE SIZING TABLE YOU HAVE SELECTED- TABLE |
| | 402.4(32) FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |