2021-04-07 08:43:12PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE #1: VALUE HAS BEEN ADJUSTED FROM $40,000.00 TO
 $57,676.00 BASED ON THE ICC BUILDING VALUATION DATA.
 NOTICE #2: UPON RE-SUBMITTAL, PROVIDE THE CORRECT
 ADDRESS ON ALL PLANS AND SPECIFICATIONS. CORRECT
 ADDRESS IS 322 N LAKESIDE CT.
  
 1. PROVIDE FINISHED FLOOR ELEVATION.
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 FINISHED FLOOR ELEVATIONS SHALL BE PLACED ON FOUNDATION
 PLAN AND/OR FLOOR PLAN.
  
 2. PROVIDE A SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 3. SOILS REPORT SUBMITTED FOR REVIEW IS FOR A 3-STORY
 STRUCTURE. PROVIDE CORRECTED SOILS REPORT WITH CORRECT
 ADDRESS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS AND
 DOORS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 5. PROVIDE ROOF SHEATHING FASTENER SCHEDULE BASED ON
 FIGURE R301.2(7) AND TABLE R301.2.(2).
 TABLE R301.2(2)
 COMPONENT AND CLADDING LOADS FOR A BUILDING WITH A MEAN
 ROOF HEIGHT OF 30 FEET LOCATED IN EXPOSURE B (ASD)
 (PSF)A, B, C, D, E, F
 TABLE R301.2(3)
 HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENTS FOR TABLE
 R301.2(2)
 FIGURE R301.2(7)
 COMPONENT AND CLADDING PRESSURE ZONES
  
 6. PROVIDE DETAIL FOR ROOF FRAMING BRACING PER
 R802.10.3.
 R802.10.3BRACING.
 TRUSSES SHALL BE BRACED TO PREVENT ROTATION AND PROVIDE
 LATERAL STABILITY IN ACCORDANCE WITH THE REQUIREMENTS
 SPECIFIED IN THE CONSTRUCTION DOCUMENTS FOR THE
 BUILDING AND ON THE INDIVIDUAL TRUSS DESIGN DRAWINGS.
  
 7. ROOFING PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  