| 2021-06-21 16:44:19 | 1) PLEASE UNDERSTAND THAT MR. TSCHOSIK IS NOT A FLORIDA | | | LICENSED ENGINEER SO HE CANNOT BE THE DESIGNER OF | | | RECORD FOR THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. PLEASE HAVE A LICENSED ENGINEER, OR THE | | | ARCHITECT FOR THE PROJECT TO SIGN AND SEAL THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS OR THE | | | MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT TO INSTALL | | | THE MECHANICAL EQUIPMENT FOR THIS PROJECT TO PRINT | | | THEIR NAME AND SIGN THE DRAWING. F.S. 471.003 | | | | | | 2) PLEASE SHOW THE RETURN PATH FROM THE NEW ROOM TO THE | | | AHU. FBC RES M1602.3 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|