2021-04-19 18:15:30ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ADDED VALUE OF $12,000 IS FOR THE MDP (1200 AMP), 2
 CENTER CHARGING CABINETS , 8 CHARGING STATIONS, AND ALL
 THE WIRING? PLEASE SUBMIT A REALISTIC VALUE FOR THE
 EQUIPMENT AND WIRING.
  
 SUBMIT LISTING FOR THE MDP CABINET SHOWING ALL THE
 EQUIPMENT ENCLOSED IN IT, 110.3
  
 SUBMIT A LISTING FOR CHARGING CABINETS 110.3
  
  