2021-04-01 09:31:00 | VEHICLE CHARGING STATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE |
| THE DRAWINGS TO SHOW THE CODE IN EFFECT (FBC 2020 USING |
| ASCE 7-16) |
| 2) RISK CATEGORY SHOWN SHOULD BE "I" - WIND SPEED FOR |
| RISK CATEGORY II WOULD BE 170MPH PER FBC WPB 120 |
| 3) ADDRESS SHOWN ON THE DRAWINGS SHOULD BE - 1801 PALM |
| BEACH LAKES BLVD. |
| 4) NO JOB VALUE IS SHOWN ON THE BUILDING PERMIT |
| APPLICATION - PLEASE REVISE THE BUILDING PERMIT |
| APPLICATION TO SHOW THE JOB COST - FBC 109.3 BUILDING |
| PERMIT VALUATIONS. IF, IN THE OPINION OF THE BUILDING |
| OFFICIAL, THE CLAIMED VALUATION |
| OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW |
| DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE |
| APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL |
| BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| ONLY LAND VALUE. |
| |