| Plan Review Notes For Permit 21030532 |
| Permit Number |
21030532 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-04-19 18:15:30 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | ADDED VALUE OF $12,000 IS FOR THE MDP (1200 AMP), 2 | | | CENTER CHARGING CABINETS , 8 CHARGING STATIONS, AND ALL | | | THE WIRING? PLEASE SUBMIT A REALISTIC VALUE FOR THE | | | EQUIPMENT AND WIRING. | | | | | | SUBMIT LISTING FOR THE MDP CABINET SHOWING ALL THE | | | EQUIPMENT ENCLOSED IN IT, 110.3 | | | | | | SUBMIT A LISTING FOR CHARGING CABINETS 110.3 | | | | | | |
|