Plan Review Notes
Plan Review Notes For Permit 21030528
Permit Number 21030528
Review Stop P
Sequence Number 1
Notes
Date Text
2021-04-20 11:11:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.RE: A3-01/DETAIL 6/ELEVATION B; ACCESSIBLE WATER
 CLOSET TO BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM
 CENTERLINE TO FINISH SIDE WALL PER FBC ACC 604.2.
  
 2.RE: A3-01/DETAIL 6/ELEVATION C; PLEASE SHOW THE
 RESTROOM MIRROR HEIGHT (TO THE REFLECTIVE SURFACE) TO
 COMPLY WITH FBC ACC 604.3.
  
 3.N/A
  
 4.REGARDING THE DRINKING FOUNTAIN. ONLY BATHROOM GROUP
 FIXTURES MAY CONNECT TO A WET VENT; SEE FBC PL 912.1.
 SANITARY RISER AND PLAN VIEW DRAWINGS DO NOT SHOW THE
 CONNECTION CONFIGURATION WITH THE TWO BACK TO BACK
 ADJACENT TOILET ROOMS. PER WPB 107.2.1, CLARIFY.
  
 5.THE NEW ACCESSIBLE WATER CLOSET (WC-1) SHALL BE WET
 VENTED BY THE NEW ACCESSIBLE LAVATORY (L-1). THE NEW
 UPSTREAM SINKS (SK-2) SHALL CONNECT DOWNSTREAM OF THE
 WET VENTED BATHROOM GROUP (WC-1 AND L-1) PER FBC PL
 912.1.
  
 6.WATER HEATER DETAIL; THE EXPANSION TANK SHALL BE
 DOWNSTREAM OF THE CHECK VALVE TO COMPLY WITH FBC PL
 607.3.
  
 7.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE SPECIFIED
 LOCHINVAR ESWO3CKD WATER HEATER. ADDITIONALLY, IF THE
 UNIT SPECIFIED IS BOTTOM FED, MODIFY THE WATER HEATER
 DETAIL TO BE IN COMPLIANCE WITH FBC PL SECTION 504.2.
  
 8.P0.1 WATER HEATER DETAIL INDICATES T & P DISCHARGE
 INDIRECT TO HEATER PAN WITH 6 INCH AIR GAP, THEN PAN
 DRAIN DISCHARGE TO BUILDING EXTERIOR OR TO NEAREST
 APPROVED INDIRECT WASTE. P1.1, NOTE 6 INDICATES
 CONNECTION TO EXISTING P&T LINE. PER WPB FBC 107.2.1,
 CLARIFY; BE SPECIFIC AS TO THE HOW THE T&P DISCHARGE
 AND PAN DRAIN ARE TO BE DEALT WITH.
  
 9.REGARDING THE HOT WATER LOOP SERVICING THE NEW
 ACCESSIBLE BATHROOM LAVATORY (L-1) AND THE THREE NEW
 SINKS (SK-2), NOTE THAT PER FBC PL 606.1 (5), EACH DOWN
 FEED PIPE IS REQUIRED TO HAVE A FULL SIZE VALVE. BY
 RUNNING THE LOOP THROUGH THE POINT OF FIXTURE OUTLET AS
 IS SHOWN ON THE RISER DIAGRAM, THIS CANNOT BE
 ACCOMPLISHED. PROVIDE INDIVIDUALLY VALVED DOWN FEED HOT
 WATER PIPES TO EACH OF THE FIXTURES FED BY THE LOOP.
  
 10.RE: P0.1; PLUMBING NOTE 26. PER WPB FBC 107.2.1,
 CLARIFY; BE SPECIFIC. REMOVE THE WORDS "OR EQUAL" AND
 SPECIFY THE THICKNESS FOR EACH OF THE APPLICATIONS
 NOTED AND SPECIFY THE VAPOR BARRIER TO BE APPLIED.
  
 11. RE: P0.1; DETAIL FOR TEMPERED AND COLD WATER SUPPLY
 CONNECTIONS FOR PUBLIC LAVATORIES. SPECIFIED 1070
 COMPLIANT VALVE IS A POINT OF USE VALVE AS 1070
 COMPLIANT VALVES TYPICALLY ARE. PER WPB FBC 107.2.1,
 REMOVE COMMENT "NOTE: ONE VALVE CAN SUPPLY A BATTERY OF
 UP TO FIVE (5) PUBLIC LAVATORIES".
  
 12. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE SPECIFIED
 RECIRCULATING PUMP.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]