| Plan Review Notes For Permit 21030504 |
| Permit Number |
21030504 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-16 15:38:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS NO INDICATIONS OFWHEE THE FENCE WILL BE | | | SPECIFICALLY LOCATED NOR ANY PROPOSED GATES AND WIDTHS | | | OF GATES. | | | | | | FIRE HYDRANTS SHOULD NOT BE BLOCKED BY THE FENCE | | | LOCATION. | | | | | | GATES FOR EMERGENCY ACCESS SHOULD NOT BE LESS THAN 20'. | | | | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | | | | 2) FOR INFORMATIONAL PURPOSES: | | | | | | KNOX PADLOCKS ARE RECOMMENDED, NOT REQUIRED, 24 HR FOR | | | EMERGENCY ACCESS AND YOUR SITE SECURITY. | | | | | | CONTACT MY OFFICE IF APPLICABLE TO INSTALL. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|