| Plan Review Notes For Permit 21030472 |
| Permit Number |
21030472 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-30 15:23:09 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT SIGNED AND SEALED DRAWINGS AND CALCULATIONS | | | FROM A FLORIDA LICENSED DESIGN PROFESSIONAL FOR WIND | | | LOAD DESIGN FOR THE LIGHT POLES AND THE FIXTURES THAT | | | WILL BE ATTACHED TO THEM. PROVIDE DETAILS SUCH AS POLE | | | HEIGHT, BURIAL DEPTH, FOUNDATION, ETC. FBC 1609 & FBC | | | 107.2.1 | | | | | | 2) SPECIFY THE WIND DESIGN DATA ON THE ENGINEER'S | | | DRAWINGS. FBC 1609 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 2021-04-30 14:15:07 | I THOUGHT THAT I PUT IN A BUILDING STOP, BUT MISSED IT. | | | JLEAHY |
|