Plan Review Notes
Plan Review Notes For Permit 21030413
Permit Number 21030413
Review Stop P
Sequence Number 3
Notes
Date Text
2023-06-01 17:31:153RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21030413
 6/1/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #1 PRINTED BELOW
 FROM THE PREVIOUS STILL EXISTS. PLEASE SHOW THE
 LOCATIONS OF THE REQUIRED POTABLE WATER BACKFLOW
 PREVENTERS FOR EACH WATER SERVICE ON THE DRAWINGS. RPZ
 BF PREVENTERS ARE REQUIRED AND SEPARATE PERMITS ARE
 REQUIRED FOR EACH. THE PLUMBING PLANS WILL NOT BE
 APPROVED UNTILTHE DEVICES ARE SHOWN ON THE PLANS AND
 SEPARATE PERMIT APPLICATIONS ARE SUBMITTED.
 YOU CAN SUBMIT APPLICATIONS TBD (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING
 COMPLETED PERMIT APPLICATIONS TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 1) SHEETS C7 & P2.1: THE LOCATIONS OF THE POTABLE WATER
 SERVICE RPZ BACKFLOW PREVENTERS ARE NOT SHOWN ON THE
 PLANS- SECTION C WPB UTILITIES CROSS-CONNECTION MANUAL.
 PLEASE LABEL THE LOCATIONS ON THE PLANS AND NOTE
 SEPARATE PERMITS ARE REQUIRED FOR EACH- SEC. 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  