| Plan Review Notes For Permit 21030413 |
| Permit Number |
21030413 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-10 16:04:52 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 21030413 | | | 2/15/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS C7 & P2.1: THE LOCATIONS OF THE POTABLE WATER | | | SERVICE RPZ BACKFLOW PREVENTERS ARE NOT SHOWN ON THE | | | PLANS- SECTION C WPB UTILITIES CROSS-CONNECTION MANUAL. | | | PLEASE LABEL THE LOCATIONS ON THE PLANS AND NOTE | | | SEPARATE PERMITS ARE REQUIRED FOR EACH- SEC. 107.2.1 | | | WPB. | | | 2) P2.1: THE REVISED PLAN REFERENCES THE ARCHITECTURAL | | | PLANS FOR DOWNSPOUT SIZES HOWEVER NO SIZES ARE | | | PROVIDED. REFER TO SECS. 1006.1 & 1008.1, AND TABLE | | | 1106.2, 1106.3, AND 1106.6 FBC P AND PROVIDE COMPLETE | | | ROOF DRAINAGE PLANS INCLUDING: | | | | | | A) ROOF SQUARE FOOT AREA AND GPM FLOW CALCULATIONS | | | BASED ON THE RAINFALL RATE. | | | B) SCUPPER AND OVERFLOW SCUPPER LOCATIONS AND SIZES. | | | C) GUTTER AND DOWNSPOUT LOCATIONS AND SIZES. | | | D) DOWNSPOUT POINTS OF CONNECTION TO STORM DRAIN MAIN. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|