Plan Review Notes
Plan Review Notes For Permit 21030413
Permit Number 21030413
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-02-15 08:59:04THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L.
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
 1) RELOCATION OF THE FIRE HYDRANT TO FRONT OF BUILDING
 PREFERRED FOR OPERATIONAL EFFICIENCY.
 ? NFPA 1 18.1.3.2 FIRE HYDRANT SYSTEMS. PLANS AND
 SPECIFICATIONS FOR
 FIRE HYDRANT SYSTEMS SHALL BE SUBMITTED TO THE FIRE
 DEPARTMENT
 FOR REVIEW AND APPROVAL PRIOR TO CONSTRUCTION.
  
  1A) FDC WAS NOT INDICATED ON THE PLANS. FOR
 OPERATIONAL EFFICIENCY, LOCATE FDC WITHIN 100 FEET OF
 THE HYDRANT.
  
  
 2) FIRE SPRINKLER PLANS WERE NOT INDICATED OR INCLUDED
 IN MASTER.
 ? FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION
 SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE
 COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING
 DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM
 INFORMATION TO BE PROVIDED ON FIRE PROTECTION
 ENGINEERING DOCUMENTS FOR WATER-BASED SYSTEMS. AS
 STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP
 THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA
 PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS
 BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER
 SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING
 DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING
 PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED
 FOR THE FIRE SPRINKLER INSTALLATION PERMIT.
  
 2A) SEPARATE PERMIT AND SHOP DRAWINGS ARE NEEDED FOR
 ANY FIRE ALARM, FIRE SPRINKLER AND UNDERGROUND
 FIRELINE.
  
 3) SHEET E2-1 ELECTRICAL PLAN SHOWS POWER GOING TO
 EMERGENCY/EXIT SIGN COMBOS BUT DOES NOT INDICATE THE
 EXIT SIGNS THAT ARE IDENTIFIED ON THE WEST SIDE
 OF THE SUITES ON SHEET LS1.0
  
  
 4) PROVIDE DIMENSIONS FOR DRIVE TO INDICATE ADEQUATE
 CLEARANCE FOR FIRE DEPARTMENT ACCESS ON SHEET SP1.0.
  
  ? NFPA 1 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS
 ROADS SHALL BE
 PROVIDED FOR EVERY FACILITY, BUILDING, OR PORTION OF A
 BUILDING
 HEREAFTER CONSTRUCTED OR RELOCATED.
  
 5) THERE IS AN INDICATION OF LIGHT FRAME TRUSS TYPE ON
 SHEET A2.1.1
 ?PER F.S. 69A-60.0081
 (1) PURPOSE: THE PURPOSE OF THIS RULE IS TO REQUIRE THE
 PLACEMENT OF AN IDENTIFYING SYMBOL ON STRUCTURES
 CONSTRUCTED WITH A LIGHT-FRAME TRUSS COMPONENT IN A
 MANNER SUFFICIENT TO WARN PERSONS CONDUCTING FIRE
 CONTROL AND OTHER EMERGENCY OPERATIONS OF THE EXISTENCE
 OF LIGHT-FRAME TRUSS-TYPE CONSTRUCTION IN THE
 STRUCTURE.
 (2) DEFINITIONS.
 (A) ?LIGHT-FRAME TRUSS-TYPE CONSTRUCTION? MEANS A TYPE
 OF CONSTRUCTION WHOSE PRIMARY STRUCTURAL ELEMENTS ARE
 FORMED BY A SYSTEM OF REPETITIVE WOOD OR LIGHT GAUGE
 STEEL FRAMING MEMBERS.
 (B) ?APPROVED SYMBOL? MEANS A MALTESE CROSS MEASURING 8
 INCHES HORIZONTALLY AND 8 INCHES VERTICALLY, OF A
 BRIGHT RED REFLECTIVE COLOR, DESIGNED IN ACCORDANCE
 WITH FIGURE 1.
 (3) ANY COMMERCIAL, INDUSTRIAL, OR MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE, WHICH
 USES HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH AN
 APPROVED SYMBOL. TOWNHOUSES ARE NOT MULTIUNIT
 RESIDENTIAL STRUCTURES AND THEREFORE NOT SUBJECT TO
 THIS RULE. EACH APPROVED SYMBOL SHALL INCLUDE WITHIN
 THE CENTER CIRCLE ONE OF THE FOLLOWING DESIGNATIONS:
 (A) STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER ?R?.
 (B) STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER ?F?.
 (C) STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS ?RF.?
 (4) THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24
 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR AND:
 (A) BE PERMANENTLY ATTACHED TO THE FACE OF THE
 STRUCTURE ON A CONTRASTING BACKGROUND, OR
 (B) BE MOUNTED ON A CONTRASTING BASE MATERIAL WHICH IS
 THEN PERMANENTLY ATTACHED TO THE FACE OF THE STRUCTURE.
 (5) THE DISTANCE ABOVE THE GRADE, WALKING SURFACE OR
 THE FINISHED FLOOR TO THE BOTTOM OF THE SYMBOL SHALL BE
 NOT LESS THAN 4 FEET (48 IN.).
 (6) THE DISTANCE ABOVE THE GRADE, WALKING SURFACE OR
 THE FINISHED FLOOR TO THE TOP OF THE SYMBOL SHALL BE
 NOT MORE THAN 6 FEET (72 IN.).
 (7) IN SINGLE TENANT STRUCTURES WITH MULTIPLE MAIN
 ENTRY DOORS, SUCH AS BIG BOX RETAIL STORES, DEPARTMENT
 STORES AND GROCERY STORES, THE AUTHORITY HAVING
 JURISDICTION IS AUTHORIZED TO REQUIRE THAT OTHER MAIN
 ENTRY DOORS OF THE STRUCTURE BE MARKED WITH AN APPROVED
 SYMBOL TO CARRY OUT THE PURPOSE IN SUBSECTION (1)
 ABOVE.
 (8) IN MULTIPLE TENANT STRUCTURES AND COVERED MALL
 STRUCTURES WITH MULTIPLE MAIN ENTRY DOORS, THE
 AUTHORITY HAVING JURISDICTION IS AUTHORIZED TO REQUIRE
 THAT OTHER MAIN ENTRY DOORS OF THE STRUCTURE BE MARKED
 WITH AN APPROVED SYMBOL TO CARRY OUT THE PURPOSE IN
 SUBSECTION (1) ABOVE.
 (9) IN MULTIPLE TENANT STRUCTURES AND COVERED MALLS
 WITH MULTIPLE MAIN ENTRY DOORS, THE AUTHORITY HAVING
 JURISDICTION IS AUTHORIZED TO REQUIRE THAT OTHER MAIN
 ENTRY DOORS BE MARKED WITH AN APPROVED SYMBOL TO CARRY
 OUT THE PURPOSE IN SUBSECTION (1) ABOVE. IN SUCH
 STRUCTURES, APPROVED SYMBOLS SHALL BE MARKED ON ONE
 SIDE OF THE STRUCTURE ONLY AND SPACED NOT CLOSER THAN
 100 FEET OR AT EACH END OF THE STRUCTURE WHEN SUCH
 STRUCTURE IS LESS THAN 100 FEET IN LENGTH.
 (10) THE OWNER OF EACH NEW STRUCTURE REQUIRED TO COMPLY
 WITH THIS SECTION SHALL MARK THE STRUCTURE WITH THE
 APPROVED SYMBOL PRIOR TO RECEIVING A CERTIFICATE OF
 OCCUPANCY.
 (11) THE OWNER OF EACH EXISTING STRUCTURE REQUIRED TO
 COMPLY WITH THIS SECTION SHALL MARK THE STRUCTURE WITH
 THE APPROVED SYMBOL WITHIN 90 DAYS OF THE EFFECTIVE
 DATE OF THIS RULE.
 (12) WHERE THE OWNER OF THE STRUCTURE AND THE AUTHORITY
 HAVING JURISDICTION DISAGREE AS TO THE USE OF
 LIGHT-FRAME TRUSS-TYPE CONSTRUCTION WITHIN THE
 STRUCTURE, THE OWNER SHALL BE GRANTED NOT MORE THAN 45
 DAYS TO PROVIDE WRITTEN VERIFICATION FROM A LICENSED
 ENGINEER OR LICENSED ARCHITECT; OTHERWISE, THE OWNER
 SHALL COMPLY WITH THE RULE.
  
 6) INFORMATIONAL NOTE: ENSURE A ACCESS (KNOX) BOX IS
 INSTALLED PER NFPA 1:
 18.2.2.1 ACCESS BOX(ES). THE AHJ SHALL HAVE THE
 AUTHORITY TO
 REQUIRE AN ACCESS BOX(ES) TO BE INSTALLED IN AN
 ACCESSIBLE LOCATION
 WHERE ACCESS TO OR WITHIN A STRUCTURE OR AREA IS
 DIFFICULT
 BECAUSE OF SECURITY. THE ACCESS BOX(ES) SHALL BE OF AN
 APPROVED
 TYPE LISTED IN ACCORDANCE WITH UL 1037.
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR