Plan Review Notes
Plan Review Notes For Permit 21030412
Permit Number 21030412
Review Stop P
Sequence Number 2
Notes
Date Text
2021-05-13 16:00:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21030412 2427 PRESIDENTIAL WAY # 904
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1.RESPONSE PROVIDED; NONE. 2ND REQUEST. BUILDING HAS
 TWENTY FOUR FLOORS (BRANCH INTERVALS); UNIT IS ON THE
 NINTH FLOOR (BRANCH INTERVAL). PER FBC PL 918.3.1,
 INDIVIDUAL AND BRANCH-TYPE AIR ADMITTANCE VALVES SHALL
 VENT ONLY FIXTURES THAT ARE ON THE SAME FLOOR LEVEL AND
 CONNECT TO A HORIZONTAL BRANCH DRAIN. WHERE THE
 HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL
 BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND
 OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL CONNECT
 TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE STACK AND
 THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED TO THE
 HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL BE SIZED
 IN ACCORDANCE WITH SECTION 906.2 AND INSTALLED IN
 ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL BE
 PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES.
 NEW COMMENT: TO BE CLEAR, THE AIR ADMITTANCE VALVE AT
 THE KITCHEN SINK SANITARY RISER DIAGRAM DOES NOT
 COMPLY.
  
 2.RESPONSE PROVIDED; NO CHANGE IN CONFIGURATION OF TUB
 AND SHOWER. THE EXISTING TUB WILL BE REPLACED BY A NEW
 TUB OF THE SAME CONFIGURATION; THE SHOWER WALLS REMAIN
 AS IS AND THE EXISTING DRAIN SHALL BE USED. P.1
 SANITARY ISOMETRIC INDICATES EXTENSION OF HORIZONTAL
 FIXTURE DRAIN PIPING TO NEW THROUGH THE SLAB LOCATIONS
 FOR THE NEW WALK-IN BATHTUB AND SHOWER. PER WPB FBC
 107.2.1, PROVIDE DETAIL FOR NEW THROUGH THE FLOOR
 PENETRATIONS SHOWING COMPLIANCE WITH FBC CHAPTER 7
 REGARDING FIRESTOP OF PENETRATIONS.
 NEW COMMENT:
 A) A2 ARCHITECTURAL STILL SHOWS THE WALK-IN TUB AND THE
 DOORLESS SHOWER IN THE MASTER BATHROOM. PER WPB FBC
 107.2.1, CLARIFY.
 A) AS THERE IS NO NEW PIPING TO TUB AND SHOWER, DELETE
 REFERENCES TO CONNECT NEW SANITARY LINES TO EXISTING
 SANITARY LINES AND NOTE PIPING FOR TUB, SHOWER AND
 WATER CLOSET AS EXISTING.
 B) PROVIDE NOTE(S) ON THE PLANS STATING NO CHANGE IN
 CONFIGURATION OF TUB AND SHOWER. THE EXISTING TUB WILL
 BE REPLACED BY A NEW TUB OF THE SAME CONFIGURATION; THE
 SHOWER WALLS REMAIN AS IS AND THE EXISTING DRAIN SHALL
 BE USED.
  
 3. RESPONSE PROVIDED; NONE. 2ND REQUEST. A.1 REGARDING
 BAR SINK: NOTE AT CLOSET WHERE BAR SINK IS TO BE
 LOCATED INDICATES REBUILD A BAR. WAS THERE A BAR SINK
 IN THIS LOCATION BEFORE. ARE THE NECESSARY PLUMBING
 ROUGH-INS ALREADY IN PLACE? IF SO, INDICATE ON P.1 PLAN
 VIEW, SHOW EXISTING STACK (WASTE OR SOIL STACK WITH
 VENT STACK OR WASTE STACK VENT) AND WATER LOCATION(S).
 IF NOT, SHOW ON PLAN VIEW LOCATION AND TYPE OF EXISTING
 STACK(S), HOT/COLD WATER PLAN VIEW FOR NEW BAR SINK
 SHOWING SOURCE, VALVES, SIZES AND ROUTING. SEE P.1, BAR
 SINK SANITARY RISER DIAGRAM COMMENT 6A.
  
 4.RESPONSE PROVIDED; NONE. 2ND REQUEST. A.1 EXISTING
 KITCHEN TO BE REMODELED DOES NOT SHOW EXISTING
 CONFIGURATION. PER WPB FBC SHOW EXISTING CONFIGURATION
 OR, IF THIS IS A PROJECT TO BE EXECUTED AT A LATER
 DATE, THEN NOTE THAT IT IS NOT PART OF THE SCOPE.
  
 5. RESPONSE PROVIDED; NONE. 2ND REQUEST. A.1 EXISTING
 MASTER BATH DOES NOT SHOW A LAVATORY. PER WPB FBC
 107.2.1, SHOW THAT THERE IS AN EXISTING LAVATORY.
  
 6. RESPONSE PROVIDED; NO CHANGE IN CONFIGURATION OF
 SHOWER. P.1 CURB AND SHOWER BASE DETAILS. PER WPB FBC
 107.2.1, PLEASE CONSOLIDATE THE CURB, LINER AND SLOPE
 DETAIL AND THE WALL AND FLOOR DETAIL INTO ONE DETAIL
 FOR THE NEW SHOWER ONLY. PROVIDE ON THE DETAIL THE
 FOLLOWING INFORMATION:
 NEW COMMENT: PROVIDED DETAIL FOR WALL AND FLOOR SHALL
 INCLUDE THRESHOLD (CURB).
  
 7. RESPONSE PROVIDED; NO CHANGE IN CONFIGURATION OF TUB
 AND SHOWER P.1 WATER RISER DIAGRAMS. PER WPB FBC
 107.2.1, PROVIDE WATER RISER DIAGRAMS OF THE AFFECTED
 AREAS INCLUDING BUT NOT NECESSARILY LIMITED TO THE
 FOLLOWING:
 A) SECOND REQUEST: WATER RISER DIAGRAM FOR NEW BAR SINK
 SHOWING SOURCE, VALVES, SIZES AND ROUTING.
 B) PROVIDE IN-WALL PIPING FOR NEW SHOWER AND WALK-IN
 BATHTUB. NOT REQUIRED AS NO RECONFIGURATION.
 NEW COMMENT:
 A) FPC PL 412.3; PROVIDE NOTE INDIVIDUAL SHOWER AND
 TUB-SHOWER COMBINATION IN WALL VALVES SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE
 B) IS THE NEW BATHTUB TO BE PROVIDED WITH A DECK
 MOUNTED FAUCET AND CONTROLS. PER WPB FBC 107.2.1,
 CLARIFY. IF DECK MOUNTED PROVIDE A DETAIL SHOWING A
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 INSTALLED TO LIMIT THE HOT WATER SUPPLIED TO THE
 TUB TO A MAXIMUM TEMPERATURE OF 120?F AS REQUIRED BY
 FPC PL 412.5. PROVIDE ACCESS TO THE SAME PER FBC PL
 606.3.
  
 8.P.1 SANITARY RISER DIAGRAMS
 A) RESPONSE PROVIDED; NONE. 2ND REQUEST. BAR SINK; PER
 FBC PL 901.2 PROVIDE VENT FOR FIXTURE TRAPS ACCORDANCE
 WITH ONE OF THE VENTING METHODS SPECIFIED IN THIS FBC
 PL CHAPTER 9. PLEASE NOTE, PER FBC PL 909.2, THE TOTAL
 FALL IN A FIXTURE DRAIN DUE TO PIPE SLOPE SHALL NOT
 EXCEED THE DIAMETER OF THE FIXTURE DRAIN, NOR SHALL THE
 VENT CONNECTION TO A FIXTURE DRAIN, EXCEPT FOR WATER
 CLOSETS, BE BELOW THE WEIR OF THE TRAP. THE VENTED
 FIXTURE DRAIN SHALL CONNECT TO HORIZONTAL FIXTURE
 BRANCH (FBC PL 710.1), A WASTE/SOIL STACK FBC PL 710.1
 OR A WASTE STACK VENT (FBC PL 913). THE VENT SHALL
 EXTEND AND CONNECT BY ONE OF THE METHODS LISTED IN FBC
 PL 905.1. IF AN AIR ADMITTANCE VALVE IS USED, IT SHALL
 COMPLY WITH FBC PL 918.3.1 SEE COMMENT 1 REGARDING
 INSTALLATION IN MULTISTORY BUILDINGS. TO BE CLEAR, AN
 AIR ADMITTANCE VALVE INSTALLED ON THE NINTH FLOOR WILL
 REQUIRE ADDITIONAL RELIEF VENT PIPING TO COMPLY.
 SEE COMMENT 3 REGARDING NOTING STACK LOCATION ON PLAN
 VIEW.
 B) RESPONSE PROVIDED; NONE. 2ND REQUEST. KITCHEN; SEE
 COMMENT 4. IF NOT INCLUDED IN THIS SCOPE, THEN PER WPB
 FBC 107.2.1, DELETE. REGARDING THE DRAWING; THE VENTED
 FIXTURE DRAIN SHALL CONNECT TO HORIZONTAL FIXTURE
 BRANCH (FBC PL 710.1), A WASTE/SOIL STACK FBC PL 710.1
 OR A WASTE STACK VENT (FBC PL 913). THE VENT SHALL
 EXTEND AND CONNECT BY ONE OF THE METHODS LISTED IN FBC
 PL 905.1. IF AN AIR ADMITTANCE VALVE IS USED, IT SHALL
 COMPLY WITH FBC PL 918.3.1. SEE COMMENT 1 REGARDING
 INSTALLATION IN MULTISTORY BUILDINGS. TO BE CLEAR, THE
 AIR ADMITTANCE VALVE AS SHOWN AT THE KITCHEN SINK
 SANITARY RISER DIAGRAM DOES NOT COMPLY.
  
 C)RESPONSE PROVIDED; NONE. 2ND REQUEST. DISHWASHER
 DRAIN TO CONNECT TO KITCHEN SINK TRAP INLET. SEE FBC
 RES P2706.2.
 D) MASTER BATHROOM; PLEASE NOTE THAT THE EXISTING CODE
 COMPLIANT INFRASTRUCTURE SHOULD ALREADY EXIST FOR THIS
 BATHROOM. NEW COMMENT: AS THERE IS NO CHANGE IN FIXTURE
 DRAIN INLET FLOOR PENETRATIONS FOR MASTER BATH TUB,
 SHOWER AND WATER CLOSET, THE SANITARY RISER DIAGRAM
 REGARDING THESE FIXTURES NEED TO BE NOTED EXISTING. THE
 SAME IS APPLICABLE TO THE LAVATORY.
 D1) RESPONSE PROVIDED; NONE. 2ND REQUEST. LAVATORY;
 PLEASE SEE COMMENT 5. PLEASE NOTE THAT THE EXISTING
 CODE COMPLIANT INFRASTRUCTURE SHOULD ALREADY EXIST FOR
 THIS BATHROOM. AS SUCH, YOU SHOULD BE ABLE TO NOTE
 CONNECT TO EXISTING PLUMBING CONNECTIONS. IF RELOCATED
 ON THE SAME WALL AND MINOR MODIFICATIONS ARE REQUIRED
 TO EXTEND OR SHORTEN PIPING, PROVIDE NOTE STATING THE
 SAME. COMPLY WITH FBC PL 909.1 FOR FIXTURE DRAIN. IF
 NOT, PLEASE SEE DRAWING COMMENTS BELOW.
 PER FBC PL 901.2 PROVIDE VENT FOR FIXTURE TRAPS
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS FBC PL CHAPTER 9. PLEASE NOTE, PER FBC PL 909.2,
 THE TOTAL FALL IN A FIXTURE DRAIN DUE TO PIPE SLOPE
 SHALL NOT EXCEED THE DIAMETER OF THE FIXTURE DRAIN, NOR
 SHALL THE VENT CONNECTION TO A FIXTURE DRAIN, EXCEPT
 FOR WATER CLOSETS, BE BELOW THE WEIR OF THE TRAP. THE
 VENTED FIXTURE DRAIN SHALL CONNECT TO HORIZONTAL
 FIXTURE BRANCH (FBC PL 710.1), A WASTE/SOIL STACK FBC
 PL 710.1 OR A WASTE STACK VENT (FBC PL 913). THE VENT
 SHALL EXTEND AND CONNECT BY ONE OF THE METHODS LISTED
 IN FBC PL 905.1. IF AN AIR ADMITTANCE VALVE IS USED, IT
 SHALL COMPLY WITH FBC PL 918.3.1 SEE COMMENT 1
 REGARDING INSTALLATION IN MULTISTORY BUILDINGS. . TO BE
 CLEAR, AN AIR ADMITTANCE VALVE INSTALLED ON THE NINTH
 FLOOR WILL REQUIRE ADDITIONAL RELIEF VENT PIPING TO
 COMPLY.
  
 9. RESPONSE PROVIDED; NONE. 2ND REQUEST. P.1 GENERAL
 PLUMBING NOTE 1; PER WPB FBC 107.2.1, CORRECT TO READ
 (PLUMBING 2020 7TH EDITION)
  
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE PRIOR REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030412 2427 PRESIDENTIAL WAY # 904
  