2021-04-01 16:23:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21030412 2427 PRESIDENTIAL WAY # 904
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.BUILDING HAS TWENTY FOUR FLOORS (BRANCH INTERVALS);
 UNIT IS ON THE NINTH FLOOR (BRANCH INTERVAL). PER FBC
 PL 918.3.1, INDIVIDUAL AND BRANCH-TYPE AIR ADMITTANCE
 VALVES SHALL VENT ONLY FIXTURES THAT ARE ON THE SAME
 FLOOR LEVEL AND CONNECT TO A HORIZONTAL BRANCH DRAIN.
 WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK, THE
 HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT
 THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR
 EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE
 STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED
 TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL
 BE SIZED IN ACCORDANCE WITH SECTION 906.2 AND INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL
 BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES.
  
 2.P.1 SANITARY ISOMETRIC INDICATES EXTENSION OF
 HORIZONTAL FIXTURE DRAIN PIPING TO NEW THROUGH THE SLAB
 LOCATIONS FOR THE NEW WALK-IN BATHTUB AND SHOWER. PER
 WPB FBC 107.2.1, PROVIDE DETAIL FOR NEW THROUGH THE
 FLOOR PENETRATIONS SHOWING COMPLIANCE WITH FBC CHAPTER
 7 REGARDING FIRESTOP OF PENETRATIONS.
  
 3. A.1 REGARDING BAR SINK: NOTE AT CLOSET WHERE BAR
 SINK IS TO BE LOCATED INDICATES REBUILD A BAR. WAS
 THERE A BAR SINK IN THIS LOCATION BEFORE. ARE THE
 NECESSARY PLUMBING ROUGH-INS ALREADY IN PLACE? IF SO
 INDICATE ON P.1 PLAN VIEW, SHOW EXISTING STACK (WASTE
 OR SOIL STACK WITH VENT STACK OR WASTE STACK VENT) AND
 WATER LOCATION(S). IF NOT, SHOW ON PLAN VIEW LOCATION
 AND TYPE OF EXISTING STACK(S), HOT/COLD WATER PLAN VIEW
 FOR NEW BAR SINK SHOWING SOURCE, VALVES, SIZES AND
 ROUTING. SEE P.1, BAR SINK SANITARY RISER DIAGRAM
 COMMENTS.
  
 4.A.1 EXISTING KITCHEN TO BE REMODELED DOES NOT SHOW
 EXISTING CONFIGURATION. PER WPB FBC SHOW EXISTING
 CONFIGURATION OR, IF THIS IS A PROJECT TO BE EXECUTED
 AT A LATER DATE, THEN NOTE THAT IT IS NOT PART OF THE
 SCOPE.
  
 5.A.1 EXISTING MASTER BATH DOES NOT SHOW A LAVATORY.
 PER WPB FBC 107.2.1, SHOW THAT THERE IS AN EXISTING
 LAVATORY.
  
 6.P.1 CURB AND SHOWER BASE DETAILS. PER WPB FBC
 107.2.1, PLEASE CONSOLIDATE THE CURB, LINER AND SLOPE
 DETAIL AND THE WALL AND FLOOR DETAIL INTO ONE DETAIL
 FOR THE NEW SHOWER ONLY. PROVIDE ON THE DETAIL THE
 FOLLOWING INFORMATION:
 A )REGARDING THE CURB, LINER AND SLOPE DETAIL, INDICATE
 WHICH APPLIES TO THE NEW SHOWER AND DELETE THE
 NON-APPLICABLE. IF NO CURB (REFERRED TO AS A THRESHOLD
 IN FBC PL 421.5.2) HOW, WILL THE WATER BE RETAINED IN
 THE SHOWER COMPARTMENT WITHOUT SHOWER DOORS. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED. IT IS NOTED THAT A
 CURB (THRESHOLD) TOP LEVEL WITH A RAISED FLOOR IS
 INDICATED ON ONE DETAIL, AND SHOWER FLOOR LINER IS
 SLOPED FROM THAT POINT TO THE DRAIN. PLEASE NOTE THAT
 THE MINIMUM SLOPE OF THE LINER TO THE DRAIN SHALL BE ?
 INCH PER FOOT (2% SLOPE).
 B)INDICATE THE HEIGHT OF THE CERAMIC WALL TILE ABOVE
 THE DRAIN INLET.
 C)SLOPE (NOTED ON WALL AND FLOOR DETAIL
 D)LINER MATERIAL (NOTED ON WALL AND FLOOR DETAIL
 E)SHOWER DRAIN MATERIAL AND TYPE (IE. PVC/C.I.WITH
 CLAMPING RING )
  
 7. P.1 WATER RISER DIAGRAMS. PER WPB FBC 107.2.1,
 PROVIDE WATER RISER DIAGRAMS OF THE AFFECTED AREAS
 INCLUDING BUT NOT NECESSARILY LIMITED TO THE FOLLOWING:
 A) WATER RISER DIAGRAM FOR NEW BAR SINK SHOWING SOURCE,
 VALVES, SIZES AND ROUTING.
 B) PROVIDE IN-WALL PIPING FOR NEW SHOWER AND WALK-IN
 BATHTUB.
  
 8.P.1 SANITARY RISER DIAGRAMS
 A)BAR SINK; PER FBC PL 901.2 PROVIDE VENT FOR FIXTURE
 TRAPS ACCORDANCE WITH ONE OF THE VENTING METHODS
 SPECIFIED IN THIS FBC PL CHAPTER 9. PLEASE NOTE, PER
 FBC PL 909.2, THE TOTAL FALL IN A FIXTURE DRAIN DUE TO
 PIPE SLOPE SHALL NOT EXCEED THE DIAMETER OF THE FIXTURE
 DRAIN, NOR SHALL THE VENT CONNECTION TO A FIXTURE
 DRAIN, EXCEPT FOR WATER CLOSETS, BE BELOW THE WEIR OF
 THE TRAP. THE VENTED FIXTURE DRAIN SHALL CONNECT TO
 HORIZONTAL FIXTURE BRANCH (FBC PL 710.1), A WASTE/SOIL
 STACK FBC PL 710.1 OR A WASTE STACK VENT (FBC PL 913).
 THE VENT SHALL EXTEND AND CONNECT BY ONE OF THE METHODS
 LISTED IN FBC PL 905.1. IF AN AIR ADMITTANCE VALVE IS
 USED, IT SHALL COMPLY WITH FBC PL 918.3.1. SEE COMMENT
 1. SEE COMMENT 3 REGARDING NOTING STACK LOCATION ON
 PLAN VIEW.
 B)KITCHEN; SEE COMMENT 4. IF NOT INCLUDED IN THIS
 SCOPE, THEN PER WPB FBC 107.2.1, DELETE. REGARDING THE
 DRAWING; THE VENTED FIXTURE DRAIN SHALL CONNECT TO
 HORIZONTAL FIXTURE BRANCH (FBC PL 710.1), A WASTE/SOIL
 STACK FBC PL 710.1 OR A WASTE STACK VENT (FBC PL 913).
 THE VENT SHALL EXTEND AND CONNECT BY ONE OF THE METHODS
 LISTED IN FBC PL 905.1. IF AN AIR ADMITTANCE VALVE IS
 USED, IT SHALL COMPLY WITH FBC PL 918.3.1. SEE COMMENT
 1.
 DISHWASHER DRAIN TO CONNECT TO KITCHEN SINK TRAP. SEE
 FBC RES P2706.2.
 C) MASTER BATHROOM; PLEASE NOTE THAT THE EXISTING CODE
 COMPLIANT INFRASTRUCTURE SHOULD ALREADY EXIST FOR THIS
 BATHROOM.
 C1) LAVATORY; PLEASE SEE COMMENT 5. PLEASE NOTE THAT
 THE EXISTING CODE COMPLIANT INFRASTRUCTURE SHOULD
 ALREADY EXIST FOR THIS BATHROOM. AS SUCH, YOU SHOULD BE
 ABLE TO NOTE CONNECT TO EXISTING PLUMBING CONNECTIONS.
 IF RELOCATED ON THE SAME WALL AND MINOR MODIFICATIONS
 ARE REQUIRED TO EXTEND OR SHORTEN PIPING, PROVIDE NOTE
 STATING THE SAME. COMPLY WITH FBC PL 909.1 FOR FIXTURE
 DRAIN. IF NOT, PLEASE SEE DRAWING COMMENTS BELOW.
 PER FBC PL 901.2 PROVIDE VENT FOR FIXTURE TRAPS
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS FBC PL CHAPTER 9. PLEASE NOTE, PER FBC PL 909.2,
 THE TOTAL FALL IN A FIXTURE DRAIN DUE TO PIPE SLOPE
 SHALL NOT EXCEED THE DIAMETER OF THE FIXTURE DRAIN, NOR
 SHALL THE VENT CONNECTION TO A FIXTURE DRAIN, EXCEPT
 FOR WATER CLOSETS, BE BELOW THE WEIR OF THE TRAP. THE
 VENTED FIXTURE DRAIN SHALL CONNECT TO HORIZONTAL
 FIXTURE BRANCH (FBC PL 710.1), A WASTE/SOIL STACK FBC
 PL 710.1 OR A WASTE STACK VENT (FBC PL 913). THE VENT
 SHALL EXTEND AND CONNECT BY ONE OF THE METHODS LISTED
 IN FBC PL 905.1. IF AN AIR ADMITTANCE VALVE IS USED, IT
 SHALL COMPLY WITH FBC PL 918.3.1. SEE COMMENT 1.
 C2) BATHTUB; PLEASE NOTE THAT THE EXISTING CODE
 COMPLIANT INFRASTRUCTURE SHOULD ALREADY EXIST FOR THIS
 BATHROOM. AS SUCH, YOU SHOULD BE ABLE TO NOTE CONNECT
 TO EXISTING PLUMBING CONNECTIONS TO EXTEND OR SHORTEN
 FIXTURE DRAINS. COMPLY WITH FBC PL 909.1. IF NOT,
 PLEASE SEE DRAWING COMMENTS BELOW.
 COMPLY WITH FBC PL 909.1 VENTING OF FIXTURE TRAP,
 DISTANCE FROM TRAP TO VENT AND FBC PL 913.1 HORIZONTAL
 WET VENTING.
 C3) SHOWER; PLEASE NOTE THAT THE EXISTING CODE
 COMPLIANT INFRASTRUCTURE SHOULD ALREADY EXIST FOR THIS
 BATHROOM. AS SUCH, YOU SHOULD BE ABLE TO NOTE CONNECT
 TO EXISTING PLUMBING CONNECTIONS TO EXTEND OR SHORTEN
 FIXTURE DRAINS. COMPLY WITH FBC PL 909.1. IF NOT,
 PLEASE SEE DRAWING COMMENTS BELOW.
 COMPLY WITH FBC PL 909.1 VENTING OF FIXTURE TRAP,
 DISTANCE FROM TRAP TO VENT AND FBC PL 913.1 HORIZONTAL
 WET VENTING.
 C4) WATER CLOSET; PLEASE NOTE THAT THE EXISTING CODE
 COMPLIANT INFRASTRUCTURE SHOULD ALREADY EXIST FOR THIS
 BATHROOM. AS SUCH, YOU SHOULD BE ABLE TO NOTE CONNECT
 TO EXISTING PLUMBING CONNECTIONS TO EXTEND OR SHORTEN
 FIXTURE DRAINS. COMPLY WITH FBC PL 909.1. IF NOT,
 PLEASE SEE DRAWING COMMENTS BELOW.
 C5)COMPLY WITH FBC PL 909.1 VENTING OF FIXTURE TRAP,
 DISTANCE FROM TRAP TO VENT AND FBC PL 913.1 HORIZONTAL
 WET VENTING.
  
 9.P.1 REGARDING NOTE THAT ALL THE EXISTING ROUGH-IN
 PLUMBING IS IN PLACE; PLEASE NOTE:
 A) THE REPLACEMENT OF THE EXISTING BATHTUB, WHICH
 APPEARS TO BE A ROMAN STYLE BATHTUB AND PROBABLY HAS A
 DECK FAUCET, WILL REQUIRE WALL PIPING MODIFICATIONS AND
 PER FBC PL 412.3, A BALANCED-PRESSURE, THERMOSTATIC OR
 COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVE THAT
 CONFORMS TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1
 INSTALLED AT THE POINT OF USE.
 B) THE REPLACEMENT OF THE EXISTING SHOWER WITH THE
 WALK-IN BATHTUB WILL ALSO REQUIRE WALL MODIFICATIONS
 AND SHALL PER FBC PL 412.5, PROVIDE HOT WATER SUPPLIED
 TO BATHTUBS AND WHIRLPOOL BATHTUBS BE LIMITED TO A
 MAXIMUM TEMPERATURE OF 120?F (49?C) BY A
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION 412.3. 412.5
  
 10.P.1 REGARDING NOTE THAT WALK-IN BATHTUB IS TO BE
 INSTALLED BY MANUFACTURER; PLEASE NOTE THAT PER THE
 REQUIREMENTS OF WPB FBC SECTION 105, THE PLUMBING
 CONTRACTOR IS RESPONSIBLE FOR THE WALK-IN BATHTUB,
 UNLESS MANUFACTURER IS A PLUMBING CONTRACTOR AS WELL,
 IN WHICH CASE THAT ENTITY SHALL PULL A SEPARATE
 PLUMBING PERMIT FOR THE TUB INSTALLATION.
  
 11.PER WPB FBC 107.2.1, SUBMIT THE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE WALK-IN
 BATHTUB.
  
 12.P.1 GENERAL PLUMBING NOTE 1; PER WPB FBC 107.2.1,
 CORRECT TO READ (PLUMBING 2020 7TH EDITION)
  
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE PRIOR REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS