Plan Review Notes
Plan Review Notes For Permit 21030412
Permit Number 21030412
Review Stop B
Sequence Number 1
Notes
Date Text
2021-03-21 14:44:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21030412
 ADD: 2427 PRESIDENTIAL WAY # 904
 CONT: MAKI CONSTRUCTION
 TEL: 561-644-1107
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY MARCH 21ST/ 2021
 ACTION: DENIED
  
 1) SHEET A-2
 1A) THE MASTER BATH SHOWS THE REMOVAL OF A TUB AND IN
 GLASS A NEW DOORLESS SHOWER. THERE ARE NO PLUMBING
 PLANS AND THE FLOOR PLAN DOES NOT INDICATE IF THE OLD
 DRAIN LOCATION IS GOING TO BE USED FOR THE NEW SHOWER.
  
 POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS IF
 THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO BE
 REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1B) NEW FLOOR PENETRATIONS. THROUGH-PENETRATIONS
 FIRESTOP SYSTEMS (HORIZONTAL ASSEMBLIES). IF A NEW
 FLOOR PENETRATION IS MADE FOR THE FUTURE SHOWER DRAIN,
 THEN YOU NEED TO SHOW COMPLIANCE WITH THE 2020 FBC-B
 SECTION 714.5.1.2. THROUGH-PENETRATIONS FIRESTOP
 SYSTEMS (HORIZONTAL ASSEMBLIES). THROUGH PENETRATIONS
 SHALL BE PROTECTED BY A THROUGH PENETRATION FIRESTOP
 SYSTEM INSTALLED IN ACCORDANCE WITH ASTM E814 OR UL
 1479. THE SYSTEM SHALL HAVE AN F RATING / T RATING OF
 NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED
 RATING OF THE FLOOR PENETRATED.
  
 1C) THE NEW DOORLESS SHOWER DOES NOT STATE THE TYPE OF
 BACKING MATERIAL TO BE INSTALLED IN THE SHOWER.
 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 1D) THE FLOOR PLAN DOES NOT PROVIDE THE HEIGHT OF THE
 FINISH MATERIAL IN THE SHOWER NOR TYPE OF MATERIAL..
 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS
 AND BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE
 FINISHED WITH A NONABSORBENT SURFACE TO A HEIGHT NOT
 LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 1E) THE PLANS ARE SILENT AS IF THERE IS TO BE A CURB IN
 THE SHOWER, PLEASE PROVIDE DETAIL OF CURB. IF NO CURB
 HOW WILL THE WATER BE RETAINED IN THE SHOWER
 COMPARTMENT WITHOUT SHOWER DOORS. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) SHEET A-1 DEMOLITION:
 2A) DESIGN CRITERIA: LIST THE OCCUPANCY TYPE AS R-3 A
 SINGLE FAMILY DWELLING TYPE. PLEASE NOTE IN THE 2020
 FBC-B SECTION 310.4 WOULD CATEGORIZE THIS OCCUPANCY AS
 R-2 APARTMENT- NON-TRANSIENT OR CONDOMINIUMS.
  
 2B) DESIGN CRITERIA: LIST THE CONSTRUCTION TYPE AS 5-B.
 PLEASE NOTE THIS BUILDING IS A 24 STORY HIGHRISE AND
 BUILDING TYPE IS I-A. 2020 FBC-B TABLE 504.3 & TABLE
 504.4.
  
 3) SHEET A-1 THE DEMOLITION SHEET NOTE 11 STATES
 INSTALL NEW FLOORING WITH SOUND PROOFING IN THE MASTER
 BEDROOM, BATHROOM, BEDROOM #3, KITCHEN AND MASTER
 BATHROOM. THE PLANS DO NOT STATE WHAT TYPE OF FLOOR
 FINISH MATERIAL IS TO BE INSTALLED.
 FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  